Powerware 8 - 10 kVA, 8 - 15 kVA Maintenance, Regular service/intervals, Scrapping, Batteries

Page 36

8. Maintenance

All operations inside the unit must be performed only by a service engineer from the manufacturer or from an agent, authorised by the manufacturer.

The troubleshooting procedure gives simple remedial if a malfunction occurs in the UPS. The operator should start the trouble shooting if there is an active alarm indicated on the LCD screen. Service should be contacted if the active alarm is abnormal and displayed as a service code.

Call service if you are not able to solve the problem.

LCD display

Description

Action

 

 

 

 

The connected load needs more

Shut down the least important load

 

that is connected to the UPS. The UPS

 

power than the UPS is rated to

Overload

should switch back to normal

provide. The inverter or static bypass

 

operation once the load level is

 

is supplying the excessive load level.

 

acceptable.

 

 

 

Your batteries are detected to be

Batteries should be replaced and you

Battery test failed

need to contact the local office or

faulty.

 

representative of the UPS manufacturer.

 

 

 

The UPS is operating in stored energy

Make controlled shutdown of the

Battery low

mode. It will shut down soon due to

protected load immediately to prevent

 

low battery voltage.

loss of data.

 

The UPS is operating in stored energy

Save your data and perform a

On battery

controlled shutdown of your server

mode.

 

load.

 

 

 

 

Check that fans are operational and

Overtemperature

High UPS temperature is detected.

ventilation holes are not blocked. Make

sure the ambient temperature is not

 

 

 

 

excessive

Table 41. Typical alarms displayed in the LCD screen of the UPS unit.

Scrapping

Before scrapping UPS or its battery cabinet, the battery bank must be removed. Local requirements must be followed in battery recycling or discard. The removal of batteries is allowed only by authorised service personnel due to high energy and voltage.

Regular service/intervals

The UPS requires very little maintenance if installed in an appropriate environment.

Maintentenance

Interval

Batteries change

~ 3-5 years / service

 

 

Batteries test

~ 18 months / service

 

 

Cooling fan change

~ 5 years / service

Table 42. Routine maintenance intervals recommended by the manufacturer.

Batteries

The condition of the batteries is crucial for operation. The UPS will indicate by audible and visual alarms if the capacity of the battery bank has decreased. The UPS units are provided with the automatic battery test and ABM management function to continuously monitor the condition of the battery bank.

36

UPS 8 – 15 kVA, 230V 50/60 Hz output

1022403

 

User’s Guide

Revision B1

Image 36
Contents Page Copyright Contents Safety instructions User precautionsAudience CE markingEnvironment InquiriesMechanical installation Delivery checkUnpacking and visual inspection Type designation label Planning before installation Equipment Weight Point DistributedCabinet installation Mechanical bypass switchMechanical bypass switch MBS when installed in the backside Transformer option External battery cabinet option Battery racksElectrical installation Location of the power terminalsPower cables and protective fuses Power terminals found in UPS unitsWiring procedure Installation procedureWiring diagram of UPS N-model 3-ph rectifier Wiring diagram of UPS NT-model 3-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier Wiring diagram of UPS ST-model 1-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier, Norway External Battery Cabinet EBC installation procedure Do not place EBC on the UPS unitUser Settings Number of Battery Strings SPM tie cabinet Dimensions of the SPM SPM9155 wiring diagram with three UPSs connected Software and connectivity Communication cablesConnection to the standard RS-232 port External control connections LanSafe softwareEmergency Power Off EPO External control cable connections to the UPSProgrammable signal inputs Relay outputsSlot communication option SNMP/Web Module optionalAS400 Relay Module optional Single Serial Port Module optionalModus/Jbus Module optional User operations Display functionsUser Settings Description Available settings Default setting GeneralConfiguring user settings Using relay outputsChanging language Changing charging currentBattery start-up Normal start-upShutdown CheckMaintenance Regular service/intervalsScrapping BatteriesLED Indicators Maintenance bypass switch MBS operationCooling fan Turn UPS from normal mode to mechanical bypass No break transfer from normal mode to Service BypassTurn UPS from mechanical bypass to normal mode No break transfer from Mechanical Bypass to normal modeTurn on S3 switch to connect UPS output to load Dimensional drawings UPS models with no battery sectionsExternal battery cabinet models with 2 and 3 sections Technical data Mechanical configurationCharacteristics StandardsAC input DC circuitAC output Warranty

8 - 15 kVA, 8 - 10 kVA specifications

Powerware 8 - 10 kVA and 8 - 15 kVA are robust uninterruptible power supply (UPS) systems designed to provide reliable power protection and enhanced performance for critical applications. These UPS systems are ideal for various business environments, including data centers, server rooms, and industrial settings.

A primary feature of the Powerware series is its modular design, which allows for easy scalability and adaptability to meet the growing power requirements of modern IT infrastructure. The systems can be configured to provide redundancy, ensuring increased reliability and uptime while delivering high-efficiency performance.

One of the standout characteristics of the Powerware 8 - 10 kVA and 8 - 15 kVA models is their advanced double-conversion technology, which offers consistent power conditioning and isolation from utility issues like voltage surges, frequency variations, and power outages. This technology ensures that connected devices receive clean, stable power, minimizing the risk of downtime caused by electrical disturbances.

Another key feature is the availability of an intuitive LCD display that provides users with real-time information about the UPS status, critical alarms, and event logs, enabling proactive management of power demands and potential issues. The systems also support remote monitoring and management through advanced communication options, allowing IT administrators to maintain oversight of the power environment from any location.

The Powerware series incorporates high-efficiency designs that help reduce energy consumption, ultimately lowering operational costs. With an input power factor of up to 0.99 and a typical efficiency exceeding 94%, these UPS units not only contribute to environmental sustainability but also enhance the overall performance of the power infrastructure.

In addition to these practical features, the Powerware 8 - 10 kVA and 8 - 15 kVA models are equipped with multiple output options, including configurable outlets and hardwire connections, offering flexibility in deployment. They also come with advanced battery management systems, which optimize battery performance, extending their lifespan and reducing maintenance efforts.

Overall, Powerware 8 - 10 kVA and 8 - 15 kVA systems are reliable choices for businesses seeking efficient and adaptable power protection solutions to support their critical operations. Their innovative technologies and comprehensive features ensure that companies can maintain productivity while safeguarding their valuable equipment and data against power disruptions.