Powerware 8 - 10 kVA, 8 - 15 kVA manual Turn UPS from normal mode to mechanical bypass

Page 38

Figure 41. The normal positions of the three MBS switches.

Turn UPS from normal mode to mechanical bypass

The procedure to turn the UPS to mechanical bypass switch is described below.

Figure 42. The normal (UPS supplying the load) positions of the three MBS switches.

No break transfer from normal mode to Service Bypass:

1.The normal start position should be following:

OFF ON ON

2.Use LCD to turn the UPS on internal static bypass mode. Remember to verify the transfer before proceeding the next step.

3.Remove the locking plate of the S1-3 switches.

4.Turn ON the S1 switch to bypass UPS:

ON

ON ON

5.Turn OFF the S3 switch to disconnect UPS output:

ON OFF

ON

6.Use LCD to turn UPS OFF.

7.Turn F1 battery breakers and F2 input to OFF position.

38

UPS 8 – 15 kVA, 230V 50/60 Hz output

1022403

 

User’s Guide

Revision B1

Image 38
Contents Page Copyright Contents Audience Safety instructionsUser precautions CE markingEnvironment InquiriesUnpacking and visual inspection Mechanical installationDelivery check Type designation label Planning before installation Equipment Weight Point DistributedCabinet installation Mechanical bypass switchMechanical bypass switch MBS when installed in the backside Transformer option External battery cabinet option Battery racksElectrical installation Location of the power terminalsPower cables and protective fuses Power terminals found in UPS unitsWiring procedure Installation procedureWiring diagram of UPS N-model 3-ph rectifier Wiring diagram of UPS NT-model 3-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier Wiring diagram of UPS ST-model 1-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier, Norway External Battery Cabinet EBC installation procedure Do not place EBC on the UPS unitUser Settings Number of Battery Strings SPM tie cabinet Dimensions of the SPM SPM9155 wiring diagram with three UPSs connected Connection to the standard RS-232 port Software and connectivityCommunication cables External control connections LanSafe softwareEmergency Power Off EPO External control cable connections to the UPSProgrammable signal inputs Relay outputsSlot communication option SNMP/Web Module optionalModus/Jbus Module optional AS400 Relay Module optionalSingle Serial Port Module optional User operations Display functionsUser Settings Description Available settings Default setting GeneralChanging language Configuring user settingsUsing relay outputs Changing charging current Shutdown Battery start-up Normal start-up CheckScrapping MaintenanceRegular service/intervals BatteriesCooling fan LED IndicatorsMaintenance bypass switch MBS operation Turn UPS from normal mode to mechanical bypass No break transfer from normal mode to Service BypassTurn UPS from mechanical bypass to normal mode No break transfer from Mechanical Bypass to normal modeTurn on S3 switch to connect UPS output to load Dimensional drawings UPS models with no battery sectionsExternal battery cabinet models with 2 and 3 sections Characteristics Technical dataMechanical configuration StandardsAC output AC inputDC circuit Warranty