Powerware 8 - 15 kVA, 8 - 10 kVA manual Wiring procedure, Installation procedure

Page 15

Contact the manufacturer’s authorised agent or the local office for assistance at fuse and cable sizing. Refer to the recommended cable and fuse ratings in the below table.

UPS rating

 

Input

 

 

Bypass

 

Load

 

PE

Battery

 

Fusing

Cable

Fusing

Cable

Cable

I nom

Cable

Cable

 

 

8 kVA

3-phase

3x16

A

3x2.5 mm²

50 A

10 mm²

10 mm²

34.8 A

10 mm²

10 mm²

 

1-phase

50 A

 

10 mm²

50 A

10 mm²

10 mm²

34.8 A

10 mm²

10 mm²

10 kVA

3-phase

3x16

A*

3x2.5 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

 

3-phase

3x20

A

3x4 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

 

1-phase

63 A

 

16 mm²

50 A

10 mm²

10 mm²

43.5 A

10 mm²

10 mm²

12 kVA

3-phase

3x25

A

3x6 mm²

63 A

16 mm²

16 mm²

52.2 A

16 mm²

10 mm²

15 kVA

3-phase

3x25

A*

3x6 mm²

80 A

25 mm²

25 mm²

65.2 A

16 mm²

10 mm²

 

3-phase

3x32

A

3x10 mm²

80 A

25 mm²

25 mm²

65.2 A

16 mm²

10 mm²

Maximum

3-phase

3x63

A

3x16 mm²

80 A

35 mm²

35 mm²

 

35 mm²

16 mm²

Table 14. Cable and fuse ratings for the different UPS ratings

(*With optional limited charging feature at low input and high kW load, see User Settings)

Wiring procedure

The power cable terminals are located in the back of the UPS unit. The service personnel is responsible for the correct electrical installation. They must be authorised by the manufacturer.

The installation procedure:

1.Remove the cover(s) of the terminal box of the power cables with a screwdriver. Refer to the dimensional drawing for the correct location at the back of the unit.

2.Slide the cables through the grommets of the connection box.

3.Connect the conductors of the rectifier and bypass input cables to the proper terminals. With single phase unit it is recommended to use the same phases for rectifier and bypass inputs.

4.Connect the conductors of the load cable to the proper terminals.

5.Connect the conductors of an external battery cabinet cable to the external battery +, - and PE terminals. Check for the correct polarity.

See External Battery Cabinet (EBC) installation procedure.

Warning!

If available, the internal battery has to be disconnected first because the external battery terminals are hazardous due to the parallel battery string.

6.Secure the cables with the grommets in the connection box.

7.Fasten the cover of the terminal box with a screwdriver.

The IEC/EN 62040-1 safety instructions require the fitting by the user of a warning label on all primary power isolators installed remote from the UPS area. The warning label for electrical maintenance personnel shall carry the following wording or equivalent:

“ISOLATE UNINTERRUBTIBLE POWER SUPPLY (UPS) BEFORE WORKING ON THIS CIRCUIT.”

A readily accessible disconnect device shall be incorporated in the building installation wiring as shown in diagrams.

1022403

UPS 8 – 15 kVA, 230V 50/60 Hz output

15

Revision B1

User’s Guide

 

Image 15
Contents Page Copyright Contents CE marking Safety instructionsUser precautions AudienceInquiries EnvironmentMechanical installation Delivery checkUnpacking and visual inspection Type designation label Equipment Weight Point Distributed Planning before installationMechanical bypass switch Cabinet installationMechanical bypass switch MBS when installed in the backside Transformer option Battery racks External battery cabinet optionLocation of the power terminals Electrical installationPower terminals found in UPS units Power cables and protective fusesInstallation procedure Wiring procedureWiring diagram of UPS N-model 3-ph rectifier Wiring diagram of UPS NT-model 3-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier Wiring diagram of UPS ST-model 1-ph rectifier Wiring diagram of UPS S-model 1-ph rectifier, Norway Do not place EBC on the UPS unit External Battery Cabinet EBC installation procedureUser Settings Number of Battery Strings SPM tie cabinet Dimensions of the SPM SPM9155 wiring diagram with three UPSs connected Software and connectivity Communication cablesConnection to the standard RS-232 port LanSafe software External control connectionsExternal control cable connections to the UPS Emergency Power Off EPORelay outputs Programmable signal inputsSNMP/Web Module optional Slot communication optionAS400 Relay Module optional Single Serial Port Module optionalModus/Jbus Module optional Display functions User operationsDescription Available settings Default setting General User SettingsChanging charging current Configuring user settingsUsing relay outputs Changing languageCheck Battery start-upNormal start-up ShutdownBatteries MaintenanceRegular service/intervals ScrappingLED Indicators Maintenance bypass switch MBS operationCooling fan No break transfer from normal mode to Service Bypass Turn UPS from normal mode to mechanical bypassNo break transfer from Mechanical Bypass to normal mode Turn UPS from mechanical bypass to normal modeTurn on S3 switch to connect UPS output to load UPS models with no battery sections Dimensional drawingsExternal battery cabinet models with 2 and 3 sections Standards Technical dataMechanical configuration CharacteristicsAC input DC circuitAC output Warranty