Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions. When replacing batteries, replace with the same type and number of batteries.
Note!
Do not dispose of batteries in a fire. The batteries may explode.
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Cooling fan
The cooling fan lifespan of the UPS unit is about 60 000 operating hours. The actual lifespan depends on the environment and ambient temperature.
Fan failure can be predicted by increasing noise from the fan bearings. The fan replacement is recommended once this symptom starts appearing.
Do not use other than manufacturer’s specified spare parts.
LED Indicators
The UPS unit has (4) LEDs to indicate the status.
Graphical sign | LED | Description | Note | ||
|
|
| Green | UPS status is ok. | Blinking when a new notice message |
|
|
| is active. | ||
|
|
|
|
| |
|
|
| Yellow 1 | UPS is in battery mode |
|
|
|
|
|
|
|
|
|
| Yellow 2 | UPS is in bypass mode |
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| Red | UPS has an active alarm | Blinking when new alarm is not reset |
|
|
| and still active. | ||
|
|
|
|
|
Table 43. Description of the LED indicators.
Maintenance bypass switch (MBS) operation
The maintenance bypass switch may be as standard or as optional in your system depending on the ordered configuration. The operation of the MBS is allowed for a trained person only who is familiar with the UPS behaviour and functions. The full UPS wiring diagram with a MBS switch is presented in the installation part of the manual.
Note!
The MBS consist of three switches and failure to understand the correct sequence may drop the critical load.