Powerware 9315 UPS operation manual 4shows the Load Amps Meters screen

Page 31

Using the Monitor Panel

AGraphics − Displays a real-time graphic representation of the flow of current through the internal UPS components.

ASetup − Allows you to configure the UPS communication port and set the date and time for the timestamp.

Figure 5-3shows the LCD screen as it appears when you first start the UPS. The Meters menu is displayed in the menu box, with the System option highlighted. In the information area, the system meters show their current readings.

 

 

Uninterruptible Power System

 

 

 

 

System Normal

 

 

 

 

 

 

04 MAY 1997

14:23:45

Alarm:

None

 

 

 

 

 

 

 

 

 

 

Notice: None

 

 

 

 

 

 

 

 

 

 

Battery

 

Input

 

 

 

Output

 

Percent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100%

VAB

VBC

VCA

FREQ

VAB

VBC

VCA

FREQ

 

 

 

 

480

480

480

60.0

480

480

480

60.0

 

 

IA

IB

 

 

IC

IA

IB

IC

IN

 

 

480

480

 

480

361

361

361

000

 

 

KVA

KW

 

 

PF

 

KVA

KW

PF

 

 

 

399

379

0.95

 

300

240

0.80

Meters

 

 

 

 

 

 

 

 

 

 

System

 

Bypass

 

 

 

Battery

 

Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

VAB

VBC

 

VCA

 

V

 

I

 

 

 

480

480

 

480

 

540

 

000

 

Meters

Events

Statistics Graphics

Setup

 

 

 

 

 

Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the kVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.

The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area displays the DC voltage (V) and the DC current (I).

Select Load Amps from the Meters menu to see a real-time bar graph of the output current of the UPS. The graph shows the current for each phase.

Figure 5-4shows the Load Amps Meters screen.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

5−5

Image 31
Contents Page Class a EMC Statements Consignes de sécuritéTable of Contents Starting and Stopping the UPS Product Specifications −1 10 Responding to System Events −1 List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Looking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelModem Output TransformerCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModeCB1 Bypass Mode Battery Mode Monitoring and Controlling UPS Operation This page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank Using the Monitor Panel System Normal 04 MAY 142345 Alarm Using the LCD ScreenAdjusting the Contrast Using the ButtonsUsing the Load Off Button Using the Menu Options Reading the Status Indicators4shows the Load Amps Meters screen Load Amps Meters Screen 5shows the Event History Log screen 6shows the Active System Events screen 7shows the Unit Statistics screen 8shows the Mimic screen −11 −12 Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Remote Monitor Panel System Normal External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationX−Slot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Rate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Change Password Adjust Output VoltageProgram Unit Name WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification −20 Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Current Product SpecificationsSystem Output Rectifier/Charger Capacity Nominal Battery This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event LightsResponding to System Events Rectifier Messages − Alarms Rectifier Messages − Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Warranty Page 164201036G