Powerware 9315 UPS operation manual Data/Stop, Handshaking, Save, Default Settings

Page 54

Communication

7.5.3 Data/Stop

The data size and stop bits of the equipment connected to this port. These settings determine the number of bits transmitted per ASCII character. The data size and stop bits you specify depend on the configuration of your equipment.

For Port 1, the data size must be set to 8, with 1 or 2 stop bits. Settings of 7 data bits/1 stop bit and 7 data bits/2 stop bits are available for Port 2.

NOTE When connecting a computer running a terminal emulation program, you should set your equipment to NO PARITY.

7.5.4 Handshaking

This setting controls handshaking. You can select XON/XOFF or Disabled for this setting.

7.5.4.1 Disabled (No Handshaking)

If handshaking is disabled, the UPS transmits and receives data via the serial port, ignoring all inputs from handshaking lines.

7.5.4.2 XON/XOFF

If handshaking is enabled, the UPS uses special characters (XON and XOFF) to handshake with the host terminal. The XON character is defined to be ASCII value 11 hex, and the XOFF character is defined to be ASCII value 13 hex. Upon receiving an XOFF command, the UPS halts transmission until an XON command is received. In the same way, if the terminal receives an XOFF command, the UPS expects the terminal to halt transmission until the UPS sends an XON command.

7.5.5 Save

Set to YES to save any changes to configuration settings upon exit from the Setup screen. Set to NO if you do not want to save any changes.

7.5.6 Default Settings

The following are the default configuration settings for the serial communication ports:

Port 1

Remote Monitor

300 baud

8/1

Handshaking Disabled

Port 2

Terminal

9600 baud

8/1

Handshaking Disabled

Each communication port on the UPS operates in one of five modes, which you select when configuring the port using the Setup Port screen.

7−8

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

Image 54
Contents Page Consignes de sécurité Class a EMC StatementsTable of Contents Starting and Stopping the UPS Product Specifications −1 10 Responding to System Events −1 List of Figures Introduction Conventions Used in This ManualFor More Information Getting HelpSafety Warnings Getting StartedTypical Powerware 9315 UPS System Power Processing Unit PPU Looking Inside the UPSControl Panel UPS Standard FeaturesMonitor Panel Communication BaysOptions and Accessories Remote Monitor Panel Power Distribution Module LV models onlyUpgrade Capability Relay Interface ModuleOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Normal Mode Understanding UPS OperationCB1 Bypass Mode Battery Mode Monitoring and Controlling UPS Operation This page intentionally left blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis page intentionally left blank Using the Monitor Panel Using the LCD Screen System Normal 04 MAY 142345 AlarmUsing the Buttons Adjusting the ContrastUsing the Load Off Button Reading the Status Indicators Using the Menu Options4shows the Load Amps Meters screen Load Amps Meters Screen 5shows the Event History Log screen 6shows the Active System Events screen 7shows the Unit Statistics screen 8shows the Mimic screen −11 −12 Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Remote Monitor Panel System Normal Battery Cabinets External Battery DisconnectRelay Interface Module UPS AvailableSupervisory Contact Module On GeneratorThis page intentionally left blank Communication Locating the Communication BaysLocation of Communication Bays on the UPS Powerware 9315 X−Slot CardsLanSafe Power Management Software Connecting Equipment to a Serial PortPin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Mode RateHandshaking Default SettingsData/Stop SaveTerminal Mode Printing Selected InformationEntire Log Ctrl+P Event History LogMeters Printout Ctrl+M System MetersBattery Test Printout Ctrl+B System Information Printout Ctrl+ASystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name Battery Test Setup WK DAY MON HrmnRemote Monitor Mode Calibration ModeComputer Mode Modify Low Battery TimeRemote Notification −20 Important Safety Instructions Maintaining the UPS SystemPerforming Preventive Maintenance E R T I S S E M E N TMaintenance Training This page intentionally left blank Product Specifications CurrentSystem Output Rectifier/Charger Capacity Nominal Battery This page intentionally left blank System Event Lights Responding to System EventsSystem Event Horns System Event MessagesResponding to System Events Rectifier Messages − Alarms Rectifier Messages − Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Warranty Page 164201036G