Powerware 9315 UPS operation manual Using the Load OFF Button

Page 79

Chapter 11

Using the LOAD OFF Button

Load Off is initiated by the covered, red LOAD OFF button on the Monitor Panel. This button is protected by a clear plastic shield to prevent accidental activation. In an emergency, you can press this button to instantaneously open the input breaker and interrupt UPS output. The UPS is cut off from utility power, and the critical load is de-energized. All power to the critical load is lost. The UPS (including Bypass) remains locked off until you reset the LOAD OFF button.

W A R N I N G

All power to the critical load is lost when you press this button. You should use this feature only in an emergency or when you want to de-energize the critical load.

To restart the UPS after pressing the LOAD OFF button, follow the procedure the UPS System after Load Off" on page 11−2 before starting the UPS.

NOTE The Remote Emergency Load Off option functions the same way as the LOAD OFF button on the Monitor Panel.

11.1Using the LOAD OFF Button

1.Raise the clear plastic shield covering the red LOAD OFF button on the Monitor Panel.

2.Press the LOAD OFF button.

The breaker and contactors open (you can hear them opening). The CB1 switch trips, and the Load Off PUSH TO RESET button on the UPS Control Panel pops out. The UPS system shuts down.

W A R N I N G

Power is present inside the UPS cabinet until the upstream input feeder circuit breaker is opened.

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

11−1

Image 79
Contents Page Class a EMC Statements Consignes de sécuritéTable of Contents Starting and Stopping the UPS Product Specifications −1 10 Responding to System Events −1 List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Looking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelModem Output TransformerCustomer Convenience Outlet Symbols, Controls, and Indicators Understanding UPS Operation Normal ModeCB1 Bypass Mode Battery Mode Monitoring and Controlling UPS Operation This page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank Using the Monitor Panel System Normal 04 MAY 142345 Alarm Using the LCD ScreenAdjusting the Contrast Using the ButtonsUsing the Load Off Button Using the Menu Options Reading the Status Indicators4shows the Load Amps Meters screen Load Amps Meters Screen 5shows the Event History Log screen 6shows the Active System Events screen 7shows the Unit Statistics screen 8shows the Mimic screen −11 −12 Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Remote Monitor Panel System Normal External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationX−Slot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Rate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BSystem Configuration Mode Main Menu System ConfigurationProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Change Password Adjust Output VoltageProgram Unit Name WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification −20 Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Current Product SpecificationsSystem Output Rectifier/Charger Capacity Nominal Battery This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event LightsResponding to System Events Rectifier Messages − Alarms Rectifier Messages − Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Warranty Page 164201036G