Powerware 9315 UPS operation manual Product Specifications, Current

Page 71

Chapter 9

Product Specifications

The UPS systems are housed in freestanding, double-front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:

Table 9-1. Model Numbers

System

Models

Notes

 

 

 

Powerware 9315 300

225 and 300 kVA

60 Hz only

 

 

 

Powerware 9315 250

200 and 250 kVA

50/60 Hz (400V models only)

 

 

 

Powerware 9315 225

225 kVA

60 Hz only

 

 

 

Powerware 9315 200

200 kVA

50/60 Hz (400V models only)

 

 

 

The following sections detail the input, output, environmental, and battery specifications for the UPS.

Table 9-2. System Input

Operating Input

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)

Voltage

400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

(Nominal +10/–15%)

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

 

 

Operating Input

"3 Hz of nominal (50 Hz or 60 Hz)

Frequency Range

 

 

 

Operating Input

Battery Charge

Current

125% of full load for overload + battery charge

 

Actual load + 25% of full load for battery charge with 0.8 pF

 

output units

 

115% of full load for overload + battery charge

 

Actual load + 15% of full load for battery charge with 0.9 pF

 

output units

 

Reduced for Generator

 

Adjustable, set to 102%

 

 

Input Current

10% THD at full load (with input filter option installed)

Harmonic Content

 

 

 

Power Walk-In

Adjustable 3–60 second rectifier ramp-up to full utility load

 

 

Power Factor

Minimum 0.95

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801-4

 

 

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

9−1

Image 71
Contents Page Class a EMC Statements Consignes de sécuritéTable of Contents Starting and Stopping the UPS Product Specifications −1 10 Responding to System Events −1 List of Figures Conventions Used in This Manual IntroductionGetting Help For More InformationGetting Started Safety WarningsTypical Powerware 9315 UPS System Looking Inside the UPS Power Processing Unit PPUCommunication Bays UPS Standard FeaturesMonitor Panel Control PanelOptions and Accessories Relay Interface Module Power Distribution Module LV models onlyUpgrade Capability Remote Monitor PanelCustomer Convenience Outlet Output TransformerModem Symbols, Controls, and Indicators Understanding UPS Operation Normal ModeCB1 Bypass Mode Battery Mode Monitoring and Controlling UPS Operation This page intentionally left blank Starting and Stopping the UPS Using the Control PanelTo Place the UPS in Normal Mode To Start the UPS in Bypass Mode To Shut Down the UPS from Normal ModeThis page intentionally left blank Using the Monitor Panel System Normal 04 MAY 142345 Alarm Using the LCD ScreenUsing the Load Off Button Using the ButtonsAdjusting the Contrast Using the Menu Options Reading the Status Indicators4shows the Load Amps Meters screen Load Amps Meters Screen 5shows the Event History Log screen 6shows the Active System Events screen 7shows the Unit Statistics screen 8shows the Mimic screen −11 −12 Building Alarm Monitoring Using Features and OptionsSummary Alarm Contacts Remote Monitor Panel System Normal External Battery Disconnect Battery CabinetsUPS Available Relay Interface ModuleOn Generator Supervisory Contact ModuleThis page intentionally left blank Locating the Communication Bays CommunicationX−Slot Cards Location of Communication Bays on the UPS Powerware 9315Connecting Equipment to a Serial Port LanSafe Power Management SoftwarePin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Rate ModeSave Default SettingsData/Stop HandshakingPrinting Selected Information Terminal ModeEvent History Log Entire Log Ctrl+PSystem Meters Meters Printout Ctrl+MSystem Information Printout Ctrl+A Battery Test Printout Ctrl+BProgram Building Alarms System ConfigurationSystem Configuration Mode Main Menu Enable/Disable Default Functions Customize Alarm Messages Program Unit Name Adjust Output VoltageChange Password WK DAY MON Hrmn Battery Test SetupModify Low Battery Time Calibration ModeComputer Mode Remote Monitor ModeRemote Notification −20 Maintaining the UPS System Important Safety InstructionsE R T I S S E M E N T Performing Preventive MaintenanceMaintenance Training This page intentionally left blank Current Product SpecificationsSystem Output Rectifier/Charger Capacity Nominal Battery This page intentionally left blank System Event Messages Responding to System EventsSystem Event Horns System Event LightsResponding to System Events Rectifier Messages − Alarms Rectifier Messages − Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Warranty Page 164201036G