Powerware 9315 UPS operation manual System Output Rectifier/Charger Capacity

Page 72

Product Specifications

Table 9-3. System Output

Rectifier/Charger Capacity

125%

 

 

DC Filtering

Ripple voltage less than 0.5% peak to peak

 

 

UPS Output Capacity

100% rated current

 

 

Output Voltage Regulation

1% (10% to 100% load)

 

 

Output Voltage Adjustment

208 Vac nominal, adjustable from 198 Vac to 218 Vac (60 Hz only)

(Nominal +/–5%)

480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)

 

600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)

 

400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)

Output Voltage Harmonic Content

3% max THD, 2% max single (linear load)

 

 

Output Voltage Balance

3% for 100% maximum load imbalance

 

 

Output Voltage Phase

3° for 100% maximum load imbalance

Displacement

 

 

 

Output Transients

"5% for 100% load step or removal

 

 

Frequency Regulation

"0.01 Hz free running

 

 

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass within

 

±0.5 Hz

 

 

Frequency Slew Rate

1 Hz per second maximum (adjustable)

 

 

Overload Capability

125% for 10 minutes

 

150% for 10 seconds

 

 

Maximum Output Capability

300% peak for 10 cycles without bypass

Table 9-4. Environmental Specifications

 

 

Operating Temperature

0 to 40°C without derating. However, operating at or near 40°C will

 

adversely affect battery life (refer to your battery specifications for more

 

information). The recommended operating temperature is 25°C.

 

 

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

 

 

Storage Temperature

–20 to +70°C (prolonged storage above 40°C will cause rapid battery

 

self-discharge)

 

 

Relative Humidity (operating and

95% maximum noncondensing

storage)

 

 

 

Acoustical Noise

65 dBA at a 1m distance

 

 

EMI Suppression

Meets FCC Regulation 47, Part 15, Subpart J, for class A devices

 

 

Electrostatic Discharge (ESD)

Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and

Immunity

with no disturbance or adverse effect to the critical load.

 

 

9−2

EATON Powerware® 9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev G www.powerware.com

Image 72
Contents Page Consignes de sécurité Class a EMC StatementsTable of Contents Starting and Stopping the UPS Product Specifications −1 10 Responding to System Events −1 List of Figures Introduction Conventions Used in This ManualFor More Information Getting HelpSafety Warnings Getting StartedTypical Powerware 9315 UPS System Power Processing Unit PPU Looking Inside the UPSUPS Standard Features Monitor PanelControl Panel Communication BaysOptions and Accessories Power Distribution Module LV models only Upgrade CapabilityRemote Monitor Panel Relay Interface ModuleOutput Transformer ModemCustomer Convenience Outlet Symbols, Controls, and Indicators Normal Mode Understanding UPS OperationCB1 Bypass Mode Battery Mode Monitoring and Controlling UPS Operation This page intentionally left blank Using the Control Panel Starting and Stopping the UPSTo Place the UPS in Normal Mode To Shut Down the UPS from Normal Mode To Start the UPS in Bypass ModeThis page intentionally left blank Using the Monitor Panel Using the LCD Screen System Normal 04 MAY 142345 AlarmUsing the Buttons Adjusting the ContrastUsing the Load Off Button Reading the Status Indicators Using the Menu Options4shows the Load Amps Meters screen Load Amps Meters Screen 5shows the Event History Log screen 6shows the Active System Events screen 7shows the Unit Statistics screen 8shows the Mimic screen −11 −12 Using Features and Options Building Alarm MonitoringSummary Alarm Contacts Remote Monitor Panel System Normal Battery Cabinets External Battery DisconnectRelay Interface Module UPS AvailableSupervisory Contact Module On GeneratorThis page intentionally left blank Communication Locating the Communication BaysLocation of Communication Bays on the UPS Powerware 9315 X−Slot CardsLanSafe Power Management Software Connecting Equipment to a Serial PortPin Assignments for Port 1 DB-9 Pin Assignments for Port 2 DB-25 Configuring the Serial Ports Mode RateDefault Settings Data/StopHandshaking SaveTerminal Mode Printing Selected InformationEntire Log Ctrl+P Event History LogMeters Printout Ctrl+M System MetersBattery Test Printout Ctrl+B System Information Printout Ctrl+ASystem Configuration System Configuration Mode Main MenuProgram Building Alarms Enable/Disable Default Functions Customize Alarm Messages Adjust Output Voltage Change PasswordProgram Unit Name Battery Test Setup WK DAY MON HrmnCalibration Mode Computer ModeRemote Monitor Mode Modify Low Battery TimeRemote Notification −20 Important Safety Instructions Maintaining the UPS SystemPerforming Preventive Maintenance E R T I S S E M E N TMaintenance Training This page intentionally left blank Product Specifications CurrentSystem Output Rectifier/Charger Capacity Nominal Battery This page intentionally left blank Responding to System Events System Event HornsSystem Event Lights System Event MessagesResponding to System Events Rectifier Messages − Alarms Rectifier Messages − Notices Monitor Panel Alarms Monitor Panel Notices Using the Load OFF Button Resetting the UPS System after Load Off Warranty Warranty Page 164201036G