11.2Cooling
Cabinet cooling must be designed by the customer so that the ambient temperature immediately surrounding the drive will not exceed temperature conditions specified in Section 7.5.1, "Temperature."
The rack, cabinet, or drawer environment for the drive must provide heat removal from the electronics and head and disc assembly (HDA). You should confirm that adequate heat removal is provided using the temper- ature measurement guidelines described in Section 7.5.1.
Forced air flow may be required to keep temperatures at or below the temperatures specified in Section 7.5.1 in which case the drive should be oriented, or air flow directed, so that the least amount of air flow resistance is created while providing air flow to the electronics and HDA. Also, the shortest possible path between the air inlet and exit should be chosen to minimize the travel length of air heated by the drive and other heat sources within the rack, cabinet, or drawer environment.
If forced air is determined to be necessary, possible
Note. Air flows in the direction shown (back to front) or in reverse direction (front to back)
Above unit
Under unit
Note. Air flows in the direction shown or in reverse direction (side to side)
Figure 9. Air flow
Above unit
Under unit
44 | Constellation SAS Product Manual, Rev. E |