Perle Systems TS2, DS1 manual Set IOChannel Digital Output, Description can be up to 20 characters

Page 76

Set IOChannel

trigger

When the trigger condition is met, triggers the specified alarm action. Triggers can be: z Disabled—No alarm settings. This is the default.

z Inactive—When the expected Digital input is active, going inactive will trigger an alarm.

z Active—When the expected Digital input is inactive, going active will trigger an alarm.

clear

Specify Manual to manually clear an alarm. Specify Auto to automatically clear the alarm when the trigger condition changes; for example, if the Trigger is Inactive and the alarm is triggered, once the input becomes active again, the alarm will be cleared when Auto is set. The default is Auto.

syslog

Sends a message to syslog when an alarm is triggered or cleared. The syslog entry includes the severity level and the value that caused the alarm to trigger or clear. The syslog message is associated with Level Critical.

 

snmp

 

Sends an SNMP trap when an alarm is triggered or cleared. The trap consists of the

 

severity level and whether the alarm was triggered or cleared.

 

description

 

Provide a description of the channel, making it easier to identify. The channel

 

description can be up to 20 characters.

 

invert-signal

 

Inverts the actual condition of the I/O signal in the status; therefore, an inactive status

 

will be displayed as active.

 

latch

 

Latches (remembers) the activity transition (active-to-inactive or inactive-to-active).

 

The latched status is maintained until it is read. Once it is read, it will revert to the

 

current status. The default is disabled.

Set IOChannel Digital Output

Description

Sets the Digital output channel settings.

User Level

Admin

Syntax

set iochannel <digital_channel>

 

[type sinksourcesink-and-source] [active-signal-width <width>]

 

[inactive-signal-width <width>]

 

[failsafe-action noneactivate-outputdeactivate-output]

 

set iochannel <digital_channel>

 

output [pulse continuouscounted <pulse_count>]

 

[active-to-inactive-delay <delay>]

 

[inactive-to-active-delay <delay>]

Options

digital_channel

Specify the Digital channel number, for example, d2.

77

Image 76
Contents Iolan DS1/TS2 EN 55022 1998, Class A, Note Table of Contents User Commands Line Commands Network Commands Time Commands Statistic Commands Set IOChannel Digital Output Serial Pins About This Book PrefaceIntended Audience Contacting Technical Support Making a Technical Support QueryRepair Procedure Feedback on this ManualCommand Syntax IntroductionIntroduction CLI ConventionsCommand Shortcuts Command OptionsServer Commands Server CommandsSet Custom-App Set ServerBypass-password Dhcp/bootpDefault size 1500 bytes Domainname Default Interval 180 seconds. monitor-connection-timeoutOem-login Password-limitTimeout Default Buffer Size 4 KB TS1Set Service Show Custom-AppShow Modbus Show ServerHardware Commands Set EthernetShow Hardware Options Auto10-half10-full100-half100-fullModbus Commands Set Modbus GatewaySet TruePort Remap-Baud TruePort Baud CommandsShow TruePort Set IPv6 IPv6 CommandsShow IPv6 Add Custom-IPv6 Set Custom-IPv6Range Default 64 method manual Range DefaultDelete Custom-IPv6 Field Format IPv6 address prefix-bits manualUser Commands Commands for Users Logged Into the IolanMenu PingResume ScreenSet User Set User SessionShow Line Users Syslog ConsoleShow Sessions Show TermtypeTelnet TcpportConfiguring Users Set Default UserVersion Add UserHotkey-prefix LevelLine-access ServiceSess-timer Phone-numberPassword Configureduser Show Default UserShow User Line Commands Port vs -Port Line CommandsLine Commands Set LineBreak-delay Dial-timeoutOptions break Break-lengthDefault Buffer Size 4 KB DS1/TS1/STS8D Default Disabled initialFlowin FlowoutReset Internet-addressKeepalive Line-nameDefault Disabled Session strings Default 10 ms Sess-timerSend-name Stop-bitsSet Line Interface Set Line Service ConfighostServerport HostportModemname Set ModemInitstring Options Program-command-line Line Service CommandsShow Line Set Telnet-Client Options termtypeSet UDP OutboundportStartipaddress EndipaddressSet Vmodem Set Vmodem-Phone Set Modbus-Slave Line Set Modbus-Master LineIpaddress HostSet Multihost Line Set Line Initiate-ConnectionShow Interface Show Telnet-ClientShow UDP Show VmodemModem Commands Add ModemDelete Modem Show ModemsPacket Forwarding Commands Set Packet-Forwarding LineEnable-end-trigger1 Enable-end-trigger2Enable-end-eof1 Enable-end-eof2Show Packet-Forwarding Line Network Commands Chapter Snmp CommandsAdd Community Add TrapDelete Trap Delete CommunitySet Snmp Set Snmp inform-timeout Set Snmp engine-id-stringSet Snmp inform-retries Show SnmpTftp Commands Hosts CommandsGateway Commands Show HostsAdd Gateway Delete GatewayDescription Configures the gateway User Level Admin Syntax Set GatewayShow Gateways DestinationipSet Syslog Logging CommandsShow Syslog Time Commands Time CommandsTime/Date Setting Commands Show Date Administration Commands Bootup CommandsSet Bootup Show BootupShow ARP Set cliTftp File Transfer Commands NetloadHostname/ipaddress FilenameCustom Factory Default Options Factory-default-configNetsave Table or a DNS serverMotd Commands SetSet Motd Show MotdStatistic Commands Chapter Configuration StatisticsShow Netstat Show Modbus StatisticsRun-Time Statistics Global I/O Commands O CommandsSet IO UDP Set IO Temperature-Scale Set LineSet IO Failsafe Set IO ModbusSet IOChannel Mode Set IOChannelSet IOChannel Digital I/O Set IOChannel Digital InputSet IOChannel Digital Input Serial Pins Current status. The default is disabled Set IOChannel Digital OutputDescription can be up to 20 characters Will be displayed as activeActive-signal-width Inactive-signal-widthActive-to-inactive-delay Inactive-to-active-delaySet IOChannel Digital Output Serial Pins Set IOChannel RelayOptions description RelaynumberSet IOChannel Analog True Analog Options analogchannelTrigger-type Trigger-levelClear-mode Clear-levelSet IOChannel Analog Temperature Level Enabled Default Disabled keepaliveSet IOChannel IOExtension Options channelClient-initiated tcp-port Client-initiated multihostServer-initiated tcp-port Local-connection inputchannelSet IOChannel Multihost Show IOChannel StatusKill IOChannel ChannelShow IO Show IOChannelChannel Control Commands Digital OutputDigital Input RelayGlossary
Related manuals
Manual 246 pages 24.21 Kb Manual 224 pages 30.96 Kb Manual 122 pages 55.83 Kb

DS1, TS2 specifications

Perle Systems TS2 and DS1 are advanced serial-to-Ethernet devices designed to facilitate seamless integration of serial devices with modern IP networks. These devices serve as crucial tools for businesses looking to enhance their communication capabilities while leveraging existing infrastructure.

One of the standout features of the Perle TS2 and DS1 is their ability to support multiple serial protocols including RS232, RS422, and RS485. This versatile support allows businesses to connect various legacy devices to their networks, ensuring that critical equipment can still communicate effectively in an increasingly digital landscape.

The TS2 model is particularly noted for its dual serial ports, enabling simultaneous communication with multiple devices. This capability is invaluable for applications requiring real-time data transmission, such as remote monitoring and automated control systems. The DS1 model, on the other hand, is designed for single-port use, making it an ideal solution for smaller-scale operations or specific single-device connections.

Both the TS2 and DS1 incorporate advanced features such as configuration through a web interface, which simplifies setup and management. Users can easily access device settings and monitor performance metrics remotely, enhancing operational efficiency. These devices also support various network protocols such as TCP/IP, UDP, and ICMP, ensuring compatibility with a wide range of network architectures.

In terms of security, Perle Systems prioritize user data protection. The TS2 and DS1 offer features including SSL encryption and SSH protection, providing an added layer of security for sensitive information transmitted over the network. This is particularly important for industries where data integrity and security are paramount, such as healthcare and finance.

Additionally, the rugged design of both devices ensures reliable performance even in harsh environments. With extended temperature ratings and robust housing, the TS2 and DS1 can operate in diverse conditions without compromising functionality.

To summarize, the Perle Systems TS2 and DS1 provide a reliable and flexible solution for connecting legacy serial devices to modern networks. With their support for multiple serial protocols, web-based management, robust security features, and rugged design, these devices cater to a variety of industries looking to modernize their communication infrastructure while maintaining existing equipment. Whether for large-scale operations or smaller implementations, the TS2 and DS1 equip businesses with the tools needed for effective serial communication in an IP-driven world.