e)Connections For The 15 D Sub Connector

Using a suitable mating connector the pins of the integrated connector should be wired as follows:

Connecting To The Integrated 15 Pin Connector

Pin Out of Integrated

Connector

PIN 7 should be connected to the Positive of the power source.

PIN 5 should be connected to the Negative ( Ground ) of the power source.

PIN 2 provides the signal output and should be connected to the positive terminal of the display, data acquisition system or voltmeter.

PIN 10 is the signal negative (ground) and should be connected to the negative (Ground) terminal of the display, data acquisition system or voltmeter.

Pin 8 is the input signal and should be connected to the positive terminal of the voltage source. The (0-5VDC) voltage control signal should be supplied from a low impedance source.

Pin 1 is the input signal negative (ground) and should be connected to the negative (Ground) terminal of the voltage source.

Pins 3, 4, 6, 9, 11, 12, 13, 14 and 15 are not used.

Caution: Avoid high voltage static discharges to the input signal connection. Do not short the output signal pins or allow them to contact the power connections at any time. DAMAGE WILL RESULT!

M-4271/0707, pg. 12 of 26

Image 12
Contents Page Page General Introduction UnpackingProduct Overview and Principle of Operation Installation General Considerations4271/0707, pg Mounting the Flow Controller Tubing ConnectionsElectrical Connections Overview Connecting The 6 Pin Mini Din Connector Connecting The 6 Pin Mini Din Connector & FMA 3000C Cable Connections For The 9 Pin D Sub Connector Connections For The 15 D Sub Connector Using a 0-5VDC Input / Output Power Adapter Package Operation Warm UpVerification of Zero Flow ReadingsQ1 / Q2 = K1 / K2 Power Save Mode Changing The Flow Rate Set-Point FMA3400/3400ST Series OnlyZero Adjustments RecalibrationChanging the Calibration Gas FMA 3400/3400ST Series Only Maintenance and Product Care GeneralReturning Units for Repair or Recalibration Specifications Series FMA FMA 3200ST FMA 3400STDimensions FMA 3400/3400ST Series 1/4 Stainless Fittings Shown Gas K Factors Gas ChemicalTroubleshooting Guide Symptom Possible Cause Method of CorrectionSymptom Possible Cause Method of Correction 4271/0707, pg 4271/0707, pg