Installation and Configuration
Figure 6 Distribution box electrical connections diagram
Mains Input
32A External Branch
CB
Input
CB
30
Mains Input
Output 32A
External
Branch
CB
Input | Byp. |
Output | |
CB | Inv. |
30 |
UPS
Output
30 CB
UPS
Output
30 CB
UPS - PFC, Battery, Inverter
UPS - PFC, Battery, Inverter
PD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same conduit.
Table 1 | Electrical specifications |
|
|
| |
|
|
|
|
|
|
Input |
| Recommended | Recommended Wire | Maximum Wire | Terminal |
Current |
| (Maximum) External | (Including ground wire) | Accepted by | Tightening |
Rating |
| Overcurrent Protection | (758C copper wire) | Terminal Block | Torque |
|
|
|
|
|
|
24A |
| 32A | 10mm2 (8AWG) | 2.26 Nm (20 |
N L | N | L |
OUTPUT |
| 32Amp Max Branch |
INPUT Overcurrent Protection |
6-10mm2 - Use Copper Wire Only
N
L N
L
OUTPUT TO LOAD | INPUT TO UPS |
NOTE
1.Note1 The installer must provide circuit breaker protection according to local codes. The mains disconnect should be within sight of the UPS or have appropriate an appropriate
2.Note 2 The installer must provide output distribution panels, circuit breaker protection, or emergency disconnects according to local codes. Output circuits must not share a common conduit with any other wiring.