Liebert GXT2-6000RT230 ON/Alarm Silence/Manual Battery Test Button, Standby/Manual Bypass Button

Page 22

Controls and Indicators

8.0CONTROLS AND INDICATORS

All indicators illuminated for illustration only.

UPStation GXT

AC INPUT BATTERY UPS ON

BYPASS

 

 

 

 

8.1ON/Alarm Silence/Manual Battery Test Button

This button controls output power to connected load(s) and has three functions:

ON

Alarm Silence

Manual Battery Test

ON - Pressing this button will start up the UPS in order to provide conditioned and protected power.

Alarm Silence - To silence alarms, press this button for at least one Second. After the alarm is silenced, the UPStation GXT2 will reactivate the alarm system to alert of additional problems.

NOTE

The LOW BATTERY and BYPASS reminder alarms CANNOT be silenced.

Manual Battery Test - To initiate a manual battery test, press the ON button for at least one second while operating from mains power with no alarm conditions present.

If only three of the five Battery LEDs illuminate, allow the UPS to recharge the batteries for 24 hours.

After 24 hours, retest the batteries.

After the batteries have been retested, if only three of the five Battery LEDs illuminate, contact your local dealer, Liebert representative or Liebert Worldwide Support Group.

8.2Standby/Manual Bypass Button

This button controls output power to connected load(s) and has dual functions:

Standby and Manual Bypass.

! CAUTION

Pressing the Standby/Manual Bypass button once will transfer the load to bypass power. Pressing the Standby/Manual Bypass button a second time within 4 seconds will cut off power to the output sockets and connected loads. Perform all necessary shutdown procedures on connected loads before pressing this button twice.

18

Image 22
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Specifications MaintenanceTroubleshooting Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC-to-DC Converter BatteryDynamic Bypass Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Storage Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedControls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Fault Indicator LED Red Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Bypass Indicator LED AmberBypass Mode Operation Normal Mode OperationBattery Mode Operation Battery Recharge ModeCommunications Pin 4 Remote Shutdown on BatteryCommunications Interface Port DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement PD-CEHDWR-Manual Bypass Switch Available Disconnect AC Power ConnectionsReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Company Behind the Products Technical Support/ServiceLocations