Liebert GXT2-6000RT230, GXT2-4500RT230 manual Battery run times

Page 34

Troubleshooting

Table 6

Battery run times

 

 

 

 

 

 

 

 

 

Load%

4500VA

6000VA

 

 

10%

125

94

 

 

20%

66

46

 

 

30%

41

29

 

 

40%

30

21

Internal Battery

50%

24

17

(minutes)

 

60%

19

13

 

 

70%

16

11

 

 

80%

14

9

 

 

90%

12

8

 

 

100%

10

7

 

 

10%

296

222

 

 

20%

166

124

 

 

30%

114

81

Internal Battery

40%

86

60

50%

70

49

+ 1 External Battery

60%

56

39

Cabinet (minutes)

70%

48

33

 

 

 

 

80%

41

28

 

 

90%

35

24

 

 

100%

31

21

 

 

10%

467

350

 

 

20%

262

197

 

 

30%

180

135

Internal Battery

40%

142

105

50%

120

85

+ 2 External Battery

60%

98

70

Cabinets (minutes)

70%

83

58

 

 

 

 

80%

72

50

 

 

90%

62

43

 

 

100%

54

38

 

 

10%

638

478

 

 

20%

358

269

 

 

30%

247

185

Internal Battery

40%

193

145

50%

164

123

+ 3 External Battery

60%

138

101

Cabinets (minutes)

70%

120

85

 

 

 

 

80%

104

73

 

 

90%

90

63

 

 

100%

80

55

 

 

10%

809

606

 

 

20%

454

341

 

 

30%

313

235

Internal Battery

40%

245

184

50%

208

156

+ 4 External Battery

60%

175

131

Cabinets (minutes)

70%

153

113

 

 

 

 

80%

135

97

 

 

90%

120

85

 

 

100%

106

75

Using the configuration program, the user may specify the number of GXT2-240VBATT external bat- tery cabinets attached to the UPS. The factory default is programmed for internal batteries only.

Table 6 above shows the estimated run times at different loads.

30

Image 34
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Specifications MaintenanceTroubleshooting Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionDC-to-DC Converter BatteryDynamic Bypass Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Storage Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedControls and Indicators ON/Alarm Silence/Manual Battery Test ButtonStandby/Manual Bypass Button Fault Indicator LED Red Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Bypass Indicator LED AmberBypass Mode Operation Normal Mode OperationBattery Mode Operation Battery Recharge ModeCommunications Pin 4 Remote Shutdown on BatteryCommunications Interface Port DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement PD-CEHDWR-Manual Bypass Switch Available Disconnect AC Power ConnectionsReconnect Indicator meanings TroubleshootingLED status Diagnosis/Audible alarm Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Company Behind the Products Technical Support/ServiceLocations