Configuration Program

7.0CONFIGURATION PROGRAM

The final step of installation may require custom configuration of your UPS using the enclosed config- uration program. Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put into full-time service powering the critical load.

For most users operating with 230VAC and with no external batteries, the factory default settings will be adequate.

7.1GXT2-6000RT230 and GXT2-4500RT230 Configuration Program Features

Select one of three L-N output voltages to match local voltages.

Enable/Disable Auto-Restart.

Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.

Set the Low Battery Warning alarm time from 2 to 30 minutes.

Enable/Disable the Auto-Battery test.

Set the Auto-Battery test to 7, 14, 21, or 28 days.

Specify the number of external battery cabinets connected to the UPS to adjust the remaining run time calculations reported by Liebert software products.

Modify the shutdown setting of DB-9 pin 6 (for information on pin assignments, see Table 2).

7.1.1What You Will Need

In addition to the GXT2 UPS, you will need the configuration program diskette and serial cable (beige or tan, 3-wire: GND, TX, RX; straight through 2-2, 3-3, 5-5) included in the UPS accessory box. A Win- dows 95® or later computer, desktop or laptop, is also required to set up and run the configuration program.

17

Image 21
Contents GXT2-6000RT230& GXT2-4500RT230 Power AvailabilityPage Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Major Components Main Frame and ElectronicsGXT2, rear view Internal Battery PacksPower distribution boxes, basic, optional Removable Power Distribution BoxWHAT’S Included GXT2 Configuration ProgramInstallation and Configuration Install the Main CabinetTower UPS Installation Rack-Mount UPS InstallationQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyM4 nuts External Battery Cabinet Installation Connect Input/Output Power Connect the Internal Batteries Using the External ConnectorStorage Distribution Box Electrical ConnectionsPD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections Electrical specificationsInitial START-UP and Electrical Checks What You Will Need Configuration ProgramON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentUPS Intelligent Communications Repo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryInternal Battery Replacement AC Power Connections PD-CEHDWR-Manual Bypass Switch Available DisconnectReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide Alarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsExternal battery cabinet specifications Model Number Power distribution specificationsSpecifications Page Technical Support/Service Company Behind the ProductsLocations