Maintenance

11.2AC Power Connections

Power connections may be disconnected from the UPS cabinet via a removable distribution box. This may be a convenient feature if the UPS must be moved a short distance or replaced. This box allows power connections to be conveniently disconnection from the main UPS cabinet. A label is attached to the UPS to describe these procedures.

Hardwire and Hardwire/Receptacle boxes that include a Manual Bypass Switch allow AC power to continue to flow from the mains input to the load while the box is removed from the UPS.

11.2.1PD-CEHDWR—Manual Bypass Switch Available Disconnect

1.DO NOT turn off the branch circuit breaker feeding power the box unless you intend to disconnect all power to the load.

2.Ensure that the Maintenance Bypass Lamp is ON.

3.Switch to the maintenance bypass position.

The Load is now unprotected from line disturbances or interruptions.

4.Turn off the UPS using the front panel controls.

a.If needed, push the OFF button for one second once to transfer the load to bypass.

b.Press the OFF button twice within four seconds to turn the UPS off.

5.Turn off the UPS input circuit breaker on the box at the rear of the UPS.

This input circuit breaker only cuts power to the connector between the box and UPS. The input circuit breaker does not cut power to the manual bypass switch.

6.Turn off the output circuit breaker on the rear of the UPS.

7.Remove the distribution box from the UPS

a.Loosen all three captive screws until box releases.

b.Pull box away from the UPS and set the box aside on a padded surface.

! CAUTION

Power is still passing through the box from mains to the load.

Reconnect

1.Align connectors and press the box onto the rear of the UPS.

2.2. Hold the box firmly against the UPS and tighten the captive screws. Do not overtighten.

3.If the Mains branch circuit breaker and load is off, turn the branch breaker on now.

4.Turn on the output circuit breaker on the rear of the UPS.

5.Turn on the input circuit breaker on the box.

6.Start the UPS according to the startup instructions. Press the ON button for one second.

7.Confirm that the UPS AVAILABLE lamp is lit beside the manual bypass switch.

8.Turn the manual bypass switch to the UPS position.

9.The UPS now protects the load.

26

Image 30
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Specifications MaintenanceTroubleshooting Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Inverter Rectifier/Power Factor Correction PFC CircuitBattery Charger System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedTower UPS Installation Install the Main CabinetInstallation and Configuration Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Storage Connect the Internal Batteries Using the External ConnectorConnect Input/Output Power Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Fault Indicator LED Red Load Level Indicators 4 Green, 1 AmberBattery Level Indicators 5 Green Bypass Indicator LED AmberBypass Mode Operation Normal Mode OperationBattery Mode Operation Battery Recharge ModeCommunications Pin 4 Remote Shutdown on BatteryCommunications Interface Port DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement AC Power Connections PD-CEHDWR-Manual Bypass Switch Available DisconnectReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Technical Support/Service Company Behind the ProductsLocations