Liebert GXT2-6000RT230, GXT2-4500RT230 manual Troubleshooting guide

Page 32

Troubleshooting

Table 4

Troubleshooting guide

 

 

 

 

Problem

Cause

Solution

 

 

 

 

UPS fails to start when the

UPS is short-circuited or

Ensure UPS is OFF. Disconnect all loads and ensure nothing is

lodged in output receptacles.

ON button is pressed.

overloaded.

Ensure loads are not defective or shorted internally.

 

 

 

 

 

UPS not plugged in.

UPS is operating from battery mode, make certain UPS is

 

 

securely plugged into the wall receptacle.

 

 

 

Battery indicator LED is

UPS input protection fuse

UPS is operating from battery mode. Save data and close

has blown/opened.

applications. Replace UPS input fuse, then restart UPS.

illuminated.

 

 

Mains voltage out of UPS

UPS is operating from battery mode. Save data and close

 

 

 

 

applications. Ensure mains supply voltage is within acceptable

 

 

input range.

 

 

limits for UPS.

 

 

 

 

 

Batteries are not fully

Keep UPS plugged in continuously at least 24 hours to

 

 

charged.

recharge batteries.

UPS has reduced battery

UPS is overloaded.

Check load level display and reduce the load on the UPS.

time.

 

 

 

 

Batteries may not be able to

Replace batteries. Contact your local dealer, Liebert

 

 

representative or the Liebert Worldwide Support Group for

 

 

hold a full charge due to age.

 

 

replacement battery kit.

Fault and Bypass indicator

UPS overloaded or load

Check load level display and remove non-essential loads.

LEDs and all load level LEDs

Recalculate the load and reduce number of loads connected to

equipment is faulty.

are illuminated.

 

UPS. Check load equipment for faults.

 

 

UPS internal fan has a

Ensure UPS is not overloaded, ventilation openings not

Fault and Bypass indicator

blocked, or room ambient temperature is not excessive. Wait

problem or UPS shutdown

LEDs and diagnostic LED A

30 minutes to allow UPS to cool, then restart UPS. If UPS does

due to temperature condition.

are illuminated.

not restart, contact your local dealer, Liebert representative or

 

 

Load is on bypass power.

the Liebert Worldwide Support Group.

 

 

 

Fault and Bypass indicator

UPS internal DC bus

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED B

overvoltage.

representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

Fault indicator LED and

 

Bus voltage under 315VDC(O/P 220VAC) / 330VDC(O/P

DC-DC failure during battery

230VAC) / 345VDC(O/P 240VAC). UPS requires service.

diagnostic LED C are

mode.

Contact your local dealer, Liebert representative or the Liebert

illuminated.

 

 

 

Worldwide Support Group.

 

 

 

Fault and Bypass indicator

UPS PFC (Power Factor

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED D

Correction Circuit) fault.

representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

Fault and Bypass indicator

 

UPS requires service. Contact your local dealer, Liebert

LEDs and diagnostic LED E

UPS inverter fault.

Representative or the Liebert Worldwide Support Group.

are illuminated.

 

 

 

Fault indicator LED and

 

Replace batteries. Contact your local dealer, Liebert

diagnostic LEDs A and C are

UPS failed the battery test.

representative or the Liebert Worldwide Support Group.

illuminated.

 

 

 

 

 

 

 

 

Your UPS has received a signal or command from the attached

Fault and Bypass indicator

UPS shutdown due to a

computer. If this was inadvertent, ensure the communication

LEDs and diagnostic LED C

command from the

cable used is correct for your system. For assistance, contact

and E are illuminated.

communications port(s).

your local dealer, Liebert representative or the Liebert

 

 

 

Worldwide Support Group.

Fault and LEDs A&E are

 

Check for external obstruction entering fan guard. UPS

Fan locked

requires service. Contact your local dealer, Liebert

Illuminated

 

 

 

representative or Liebert Worldwide Support Group.

 

 

 

Fault and LEDs B&C are

REPO active

circuit is closed. If not used, a wire jumper must connect the

Illuminated

 

REPO terminals.

 

 

 

 

UPS is OFF due to previous

 

Fault and LEDs B&D are

REPO shutdown, but the

Start the UPS using the front panel.

REPO has been connected

Illuminated

 

 

or reset. Autorestart

 

 

 

 

 

 

disabled.

 

28

Image 32
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Connect the Internal Batteries Using the External Connector Connect Input/Output PowerStorage Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedStandby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement Reconnect AC Power ConnectionsPD-CEHDWR-Manual Bypass Switch Available Disconnect LED status Diagnosis/Audible alarm TroubleshootingIndicator meanings Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Locations Technical Support/ServiceCompany Behind the Products