Troubleshooting
Table 4 | Troubleshooting guide |
| ||
|
|
| ||
Problem | Cause | Solution | ||
|
|
|
| |
UPS fails to start when the | UPS is | Ensure UPS is OFF. Disconnect all loads and ensure nothing is | ||
lodged in output receptacles. | ||||
ON button is pressed. | overloaded. | |||
Ensure loads are not defective or shorted internally. | ||||
|
|
| ||
|
| UPS not plugged in. | UPS is operating from battery mode, make certain UPS is | |
|
| securely plugged into the wall receptacle. | ||
|
|
| ||
Battery indicator LED is | UPS input protection fuse | UPS is operating from battery mode. Save data and close | ||
has blown/opened. | applications. Replace UPS input fuse, then restart UPS. | |||
illuminated. |
| |||
| Mains voltage out of UPS | UPS is operating from battery mode. Save data and close | ||
|
| |||
|
| applications. Ensure mains supply voltage is within acceptable | ||
|
| input range. | ||
|
| limits for UPS. | ||
|
|
| ||
|
| Batteries are not fully | Keep UPS plugged in continuously at least 24 hours to | |
|
| charged. | recharge batteries. | |
UPS has reduced battery | UPS is overloaded. | Check load level display and reduce the load on the UPS. | ||
time. |
|
|
| |
| Batteries may not be able to | Replace batteries. Contact your local dealer, Liebert | ||
|
| representative or the Liebert Worldwide Support Group for | ||
|
| hold a full charge due to age. | ||
|
| replacement battery kit. | ||
Fault and Bypass indicator | UPS overloaded or load | Check load level display and remove | ||
LEDs and all load level LEDs | Recalculate the load and reduce number of loads connected to | |||
equipment is faulty. | ||||
are illuminated. |
| UPS. Check load equipment for faults. | ||
|
| UPS internal fan has a | Ensure UPS is not overloaded, ventilation openings not | |
Fault and Bypass indicator | blocked, or room ambient temperature is not excessive. Wait | |||
problem or UPS shutdown | ||||
LEDs and diagnostic LED A | 30 minutes to allow UPS to cool, then restart UPS. If UPS does | |||
due to temperature condition. | ||||
are illuminated. | not restart, contact your local dealer, Liebert representative or | |||
|
| Load is on bypass power. | the Liebert Worldwide Support Group. | |
|
|
| ||
Fault and Bypass indicator | UPS internal DC bus | UPS requires service. Contact your local dealer, Liebert | ||
LEDs and diagnostic LED B | ||||
overvoltage. | representative or the Liebert Worldwide Support Group. | |||
are illuminated. | ||||
|
| |||
Fault indicator LED and |
| Bus voltage under 315VDC(O/P 220VAC) / 330VDC(O/P | ||
230VAC) / 345VDC(O/P 240VAC). UPS requires service. | ||||
diagnostic LED C are | ||||
mode. | Contact your local dealer, Liebert representative or the Liebert | |||
illuminated. |
| |||
|
| Worldwide Support Group. | ||
|
|
| ||
Fault and Bypass indicator | UPS PFC (Power Factor | UPS requires service. Contact your local dealer, Liebert | ||
LEDs and diagnostic LED D | ||||
Correction Circuit) fault. | representative or the Liebert Worldwide Support Group. | |||
are illuminated. | ||||
|
| |||
Fault and Bypass indicator |
| UPS requires service. Contact your local dealer, Liebert | ||
LEDs and diagnostic LED E | UPS inverter fault. | |||
Representative or the Liebert Worldwide Support Group. | ||||
are illuminated. |
| |||
|
| |||
Fault indicator LED and |
| Replace batteries. Contact your local dealer, Liebert | ||
diagnostic LEDs A and C are | UPS failed the battery test. | |||
representative or the Liebert Worldwide Support Group. | ||||
illuminated. |
|
| ||
|
|
| ||
|
|
| Your UPS has received a signal or command from the attached | |
Fault and Bypass indicator | UPS shutdown due to a | computer. If this was inadvertent, ensure the communication | ||
LEDs and diagnostic LED C | command from the | cable used is correct for your system. For assistance, contact | ||
and E are illuminated. | communications port(s). | your local dealer, Liebert representative or the Liebert | ||
|
|
| Worldwide Support Group. | |
Fault and LEDs A&E are |
| Check for external obstruction entering fan guard. UPS | ||
Fan locked | requires service. Contact your local dealer, Liebert | |||
Illuminated |
| |||
|
| representative or Liebert Worldwide Support Group. | ||
|
|
| ||
Fault and LEDs B&C are | REPO active | circuit is closed. If not used, a wire jumper must connect the | ||
Illuminated |
| REPO terminals. | ||
|
| |||
|
| UPS is OFF due to previous |
| |
Fault and LEDs B&D are | REPO shutdown, but the | Start the UPS using the front panel. | ||
REPO has been connected | ||||
Illuminated |
| |||
| or reset. Autorestart |
| ||
|
|
| ||
|
| disabled. |
|
28