Liebert GXT2-6000RT230, GXT2-4500RT230 manual Specifications, UPS specifications

Page 36

Specifications

13.0SPECIFICATIONS

Table 7

UPS specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

Model Number

GXT2-6000RT230

 

 

 

 

GXT2-4500RT230

 

Model Rating

6KVA / 4,200W

 

 

 

 

4.5KVA / 3,150W

Dimensions mm (in.)

 

 

 

 

 

 

 

Unit, W x D x H

221 x 547 x 430 (8.7 x 21.5 x 16.9)

 

Shipping, W x D x H

560 x 690 x 500 (22.05 x 27.17 x 19.7)

Weight kg (lbs)

 

 

 

 

 

 

 

Unit

67 (151)

 

 

 

 

67 (151)

 

Shipping

79.5 (175.3)

 

 

 

 

79.5 (175.3)

Input AC Parameters

 

 

 

 

 

 

 

Nominal Operating Frequency

50 or 60Hz (Factory Default = 50)

 

Factory Default VAC

230VAC

 

 

 

User Configurable VAC

220/230/240VAC

 

 

(May be modified using configuration program)

 

 

Operating Voltage Range Without

176 – 276VAC

 

 

 

Battery Operation

 

 

 

 

 

 

 

 

 

 

Maximum Allowable VAC

276VAC

 

 

Input Frequency Without Battery

40 - 70Hz

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

Input Power Connection

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

Output AC Parameters

 

 

 

 

 

 

 

Factory Default VAC

230VAC

 

 

 

Output Connections

PD-CEHDWR Standard (See 3.3 - Removable Power Distribution Box)

 

Frequency

50Hz or 60Hz, Nominal

 

Waveform

Sinewave

 

 

 

Main Mode

>200% for 96 milliseconds; 131 - 199% for 2 seconds;

 

Overload

112- 129% for 10 seconds with transfer to bypass

Battery Parameters

 

 

 

 

 

 

 

Type

Valve-regulated, non-spillable, lead acid

 

Quantity x V

20 x 12V

 

 

 

Battery Mfr. / Part #

Yuasa / REW 28-12

 

Back-up Time

See Table 6 - Battery run times

Recharge Time (Internal Batteries)

3 hrs. to 90% capacity after full discharge into 100% load

Bypass Protection Limits

 

 

 

 

 

 

 

Disable Bypass operation

If input voltage exceeds ±15% of the nominal voltage

 

Re-enable Bypass operation

If input voltage returns to within ±10% of nominal output voltage

 

Disable Bypass operation

When the input frequency prevents synchronous operation

Environmental

 

 

 

 

 

 

 

Operating Temperature

0°C to +40°C (+32°F to +104° F)

 

Storage Temperature

-15°C to +50°C (+5°F to +122° F)

 

Relative Humidity

0-95% non-condensing

 

Operating Elevation

Up to 2000m (6600 ft) at 40

°

C (104

°

F) without derating

 

 

 

 

 

Storage Elevation

15,000m (50,000 ft.) maximum

 

Audible Noise

<55 dBA, at 1 meter from the rear

 

<50 dBA, at 1 meter from the front or sides

 

 

Agency

 

 

 

 

 

 

 

Safety

EN62040-1-1; TUV/GS

 

EMI/EMC/C-Tick EMC

EN50091-2 and AS 62040-2: 2002, Class A; CE EMC Directive

 

ESD

EN61000-4-2, Level 4, Criteria A

 

Radiated Susceptibility

EN61000-4-3, Level 3, Criteria A

 

Electrical Fast Transient

EN61000-4-4, Level 4, Criteria A

 

Surge Immunity

EN61000-4-5, Level 3, Criteria A

 

Transportation

ISTA Procedure 1B

32

Image 36
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Connect the Internal Batteries Using the External Connector Connect Input/Output PowerStorage Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement AC Power Connections PD-CEHDWR-Manual Bypass Switch Available DisconnectReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Technical Support/Service Company Behind the ProductsLocations