Liebert GXT2-4500RT230, GXT2-6000RT230 manual Important Safety Instructions

Page 5

IMPORTANT SAFETY INSTRUCTIONS

SAVE THESE INSTRUCTIONS

This Manual Contains Important Safety Instructions. Read all safety and operating instructions before operating the Uninterruptible Power Supply (UPS). Adhere to all warnings on the unit and in this manual. Follow all operating and user instructions. This equipment can be operated by individu- als without previous training.

This product is designed for Commercial/Industrial use only. It is not intended for use with life sup- port and other designated “critical” devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is designed for data processing equipment. If uncertain, consult your dealer.

See Limited Warranty.

This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply, for installation by qualified personnel. A qualified electrician must review and approve customer sup- plied wiring, circuit breakers, intended loads, and verify correct input, output and earth connections to ensure compliance with technical standards and local electrical codes of practice. Installation instructions and warning notices only for use by qualified personnel are located after the UPS opera- tor instructions in this manual.

! WARNING

This UPS should not be supplied from electrical power systems of the “IT” (Impédance à Terre) type. (IEC 364-ELECTRICAL INSTALLATION OF BUILDINGS)

ELECTROMAGNETIC COMPATIBILITY—This UPS complies with the requirements of the EMC Directive 89/336/EEC and the published technical standards. Continued compliance requires installa- tion in accordance with these instructions and the use of manufacturer approved accessories only.

! WARNING

This is a product for restricted sales distribution to informed partners. Installation restrictions or additional measures may be needed to prevent radio interference.

Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C

(32-104°F). Install it in a clean environment, free from moisture, flammable liquids, gases and corro- sive substances.

This UPS contains no user serviceable parts. The UPS ON/OFF push buttons do not electrically iso- late internal parts. Under no circumstances attempt to gain access internally, due to the risk of elec- tric shock or burn.

Do not continue to use the UPS if the front panel indications are not in accordance with these operat- ing instructions, or the UPS performance alters in use. Refer all faults to your dealer.

Only trained engineers authorized by Liebert should perform troubleshooting. To replace batteries, refer all servicing to qualified service personnel. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal requirements.

Never block or insert any object into the ventilation holes or other openings.

DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for example: electric drills, vacuum cleaners, laser printers, hairdryers or any appliance using half wave rectification.

Storing magnetic media on top of the UPS may result in data loss or corruption.

Turn the off UPS and isolate the UPS before cleaning. Use only a soft cloth, never liquid or aerosol cleaners.

1

Image 5
Contents GXT2-6000RT230& GXT2-4500RT230 Power AvailabilityPage Table of Contents Troubleshooting MaintenanceSpecifications Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDynamic Bypass BatteryDC-to-DC Converter Major Components Main Frame and ElectronicsGXT2, rear view Internal Battery PacksPower distribution boxes, basic, optional Removable Power Distribution BoxWHAT’S Included GXT2 Configuration ProgramInstallation and Configuration Install the Main CabinetTower UPS Installation Rack-Mount UPS InstallationQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyM4 nuts External Battery Cabinet Installation Connect Input/Output Power Connect the Internal Batteries Using the External ConnectorStorage Distribution Box Electrical ConnectionsPD-CEHDWR and PD-CEHDWRBYP Terminal Block Connections Electrical specificationsInitial START-UP and Electrical Checks What You Will Need Configuration ProgramStandby/Manual Bypass Button ON/Alarm Silence/Manual Battery Test ButtonControls and Indicators Battery Level Indicators 5 Green Load Level Indicators 4 Green, 1 AmberFault Indicator LED Red Bypass Indicator LED AmberBattery Mode Operation Normal Mode OperationBypass Mode Operation Battery Recharge ModeCommunications Interface Port Pin 4 Remote Shutdown on BatteryCommunications DB-9 pin assignmentUPS Intelligent Communications Repo switch connection diagram Remote Emergency Power OffMaintenance Internal BatteryInternal Battery Replacement Reconnect AC Power ConnectionsPD-CEHDWR-Manual Bypass Switch Available Disconnect LED status Diagnosis/Audible alarm TroubleshootingIndicator meanings Troubleshooting guide Alarm conditions Troubleshooting guide cont’dBattery run times Auto-Learning Battery Run Times UPS specifications SpecificationsExternal battery cabinet specifications Model Number Power distribution specificationsSpecifications Page Locations Technical Support/ServiceCompany Behind the Products