Liebert GXT2-6000RT230 manual Normal Mode Operation, Battery Mode Operation, Bypass Mode Operation

Page 24
AC INPUT BAT
UPS ON
Normal Mode Operation Batteries at 100% Charge Load at 10%
Battery Mode Operation Batteries at 30% Charge Load at 50%

Operating Instructions

9.0OPERATING INSTRUCTIONS

9.1Normal Mode Operation

During normal operation, mains power provides energy to the UPS. The filters, power factor correction circuit and the inverter process this power to provide computer grade power to connected loads. The UPS maintains the batteries in a fully charged state. The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the UPS will sound an audible alarm. The display template indicates the percentage of load (10% of load shown in example) on the UPS output.

AC INPUT BATTERY UPS ON BYPAS S

9.2Battery Mode Operation

Battery mode occurs in event of an extreme input voltage condition

or complete mains failure. The battery system supplies power through the DC to DC converter to the inverter to generate power for the connected load. During battery mode an alarm sounds every 10 seconds. This will change to two beeps every 5 seconds

when the battery runs low (approximately 2 minutes remaining, but this is user configurable). The AC Input LED will extinguish,

and the Battery LED will illuminate to warn that a mains problem has occurred. Each battery level indicator represents a 20% capac- ity level. As capacity decreases, fewer indicators remain illumi- nated. Refer to 12.0 - Troubleshooting. For approximate battery

run times, refer to Table 6. These times are approximate, based on resistive load and an ambient temperature of 25°C (77°F). To increase this time, turn off non-essential pieces of equipment (such as idle computers and monitors) or add the optional external battery cabinet.

! CAUTION

Turning OFF the UPS while in it is battery mode will cut off output power.

9.3Bypass Mode Operation

Bypass mode occurs when the OFF button is pressed once while

the UPS is in Normal Mode. During bypass operation, mains power provides energy to the UPS. The mains power bypasses the inverter and provides power for the connected load.

The four green load level LEDs indicate an approximate level of load in 25% increments. If the UPS becomes loaded beyond full rating, the fifth (amber) LED indicator will illuminate and the

UPS will sound an audible alarm. The display template indicates

the percentage of load (26-50% of load shown in the example above) on the UPS output.

BYPAS S

9.4Battery Recharge Mode

Once mains power is restored, the UPS resumes normal operation. At this time, the Battery Charger begins recharging.

20

Image 24
Contents Power Availability GXT2-6000RT230& GXT2-4500RT230Page Table of Contents Maintenance TroubleshootingSpecifications Operating InstructionsImportant Safety Instructions Glossary of Symbols Introduction Rectifier/Power Factor Correction PFC Circuit Battery ChargerInverter System DescriptionBattery DC-to-DC ConverterDynamic Bypass Main Frame and Electronics Major ComponentsInternal Battery Packs GXT2, rear viewRemovable Power Distribution Box Power distribution boxes, basic, optionalGXT2 Configuration Program WHAT’S IncludedInstall the Main Cabinet Installation and ConfigurationTower UPS Installation Rack-Mount UPS InstallationInstalling the Adjustable Rack-Mount Kit-Sold Separately QuantityM4 nuts External Battery Cabinet Installation Connect the Internal Batteries Using the External Connector Connect Input/Output PowerStorage Distribution Box Electrical ConnectionsElectrical specifications PD-CEHDWR and PD-CEHDWRBYP Terminal Block ConnectionsInitial START-UP and Electrical Checks Configuration Program What You Will NeedON/Alarm Silence/Manual Battery Test Button Controls and IndicatorsStandby/Manual Bypass Button Load Level Indicators 4 Green, 1 Amber Battery Level Indicators 5 GreenFault Indicator LED Red Bypass Indicator LED AmberNormal Mode Operation Battery Mode OperationBypass Mode Operation Battery Recharge ModePin 4 Remote Shutdown on Battery Communications Interface PortCommunications DB-9 pin assignmentUPS Intelligent Communications Remote Emergency Power Off Repo switch connection diagramInternal Battery MaintenanceInternal Battery Replacement AC Power Connections PD-CEHDWR-Manual Bypass Switch Available DisconnectReconnect Troubleshooting Indicator meaningsLED status Diagnosis/Audible alarm Troubleshooting guide Troubleshooting guide cont’d Alarm conditionsBattery run times Auto-Learning Battery Run Times Specifications UPS specificationsPower distribution specifications External battery cabinet specifications Model NumberSpecifications Page Technical Support/Service Company Behind the ProductsLocations