Liebert GXT3-10000T220 user manual External Electrical Connections, Connecting Utility and Load

Page 13

Installation

3.4External Electrical Connections

The external electrical connections may be accessed by removing the protective panel on the rear of the UPS (see Figure 2) (panel ships loose from factory). Select a conduit knockout appropriate for your cabling, based on local electrical codes.

! WARNING

Before removing electric protective panel, ensure that the UPS is isolated.

Figure 4 Side view

Rear Panel

Cable Entry Cover

NOTE

Once installation has been completed, adjust leveling feet to prevent the UPS from moving.

3.5Connecting Utility and Load

Connect the utility supply to the input terminals of the UPS. If the Liebert® GXT3-10000T220is supplied by single-phase utility, connect the live phase to input L1.

3.6Terminal Blocks for UPS

! CAUTION

Power is connected through the input breaker, even when the UPS is in bypass mode. Opening the input breaker when in bypass mode will disconnect output power to the connected load.

Figure 5 Single source input supply—input and output connections

 

UPS Input ~

 

 

 

 

 

 

 

 

Bypass Input ~

 

 

Output ~

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BYP

L1

L2

 

 

 

 

 

 

 

 

L1

L2

 

GET

X1

X2

X3

X4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Feed

120

208 220

120

Jumper

240

0

9

Image 13
Contents Liebert GXT3-10000T220 Page Table of Contents Communication MaintenanceImportant Safety Instructions Page Information for the Protection of the Environment Leakage CurrentLiebert GXT3-10000T220 control panel Introduction and System DescriptionDevice Overview Type Model # Nominal powerOverview of UPS devices and batteries Inspection Required Setup EquipmentUnpacking Unpacking the UPS and Site PreparationEnvironmental Conditions Access to AreaFloor Loading Inventory ListElectrical preparations InstallationSuggested Cable Sizes External Protection and Isolating DevicesExternal Electrical Connections Connecting Utility and LoadTerminal Blocks for UPS Rear Panel Cable Entry CoverJumper removed for clarity Input and Output Connection RequirementsExternal Battery Cabinets Connecting Power CablesCabinet Operation Block DiagramControl Panel Fault Battery UPS On BypassControls and Messages Lighted LEDs Flashing LEDMenu tree Displayed text-system block and main menu Battery setup parameters Battery Setup ParametersControl Test ReportFault indicators Fault IndicatorsFault Cause Corrective steps UPS Shutdown Procedure Initial UPS Startup ProcedureMaintenance Bypass Procedure Maintenance Breaker, Off Position Return from Maintenance BypassBattery Test Self-TestsCleaning Test, Replacement and Disposal of BatteriesMaintenance Replacement battery packCommunication Interface Port Any Mode ShutdownDry Contact CommunicationOn Battery Battery Mode ShutdownLow Battery Liebert IntelliSlot Communication CardsRepo switch connection diagram Remote Emergency Power OffLiebert MultiLink Troubleshooting guide TroubleshootingProblem Possible Cause Solution Liebert GXT3 specifications SpecificationsTypical battery run times for the Liebert GXT3-10000T230 Battery cabinet specificationsDimensions, W x D x H, in. mm Internal Battery ParametersProduct Warranty Registration Is t Ne tTwor k Care