Liebert GXT3-10000T220 Liebert IntelliSlot Communication Cards, Battery Mode Shutdown, On Battery

Page 26

Communication

6.2.2Battery Mode Shutdown

Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.

Battery Mode Shutdown can be performed locally or remotely:

Local Battery Mode shutdown can be performed by shorting the pins in Set 4.

Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4 and mounted at remote location.

Activation of the Battery Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed by NO contact.

The current limited source (+12VDC, 50mA) will be available from UPS.

The connection to the Liebert® GXT3for remote connection will be via terminal block connector.

Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

This signal must last for 1.5 seconds or longer.

A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be stopped once triggered. If the utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

6.2.3On Battery

On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this dry contact will be closed.

6.2.4Low Battery

Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.

NOTE

The rated values for the dry contacts are:

Rated Voltage: 30V (AC or DC)

Rated Current: 300mA

6.3Liebert IntelliSlot® Communication Cards

The Liebert IntelliSlot port accepts three optional cards:

Liebert IntelliSlot SNMP Card

Liebert IntelliSlot Relay Card

Liebert IntelliSlot 485 Card.

The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers support for built-in shutdown for AS/400 systems.

The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.

Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional ancillary product for the Liebert GXT3. These instructions are available at

multilink.liebert.com

22

Image 26
Contents Liebert GXT3-10000T220 Page Table of Contents Maintenance CommunicationImportant Safety Instructions Page Leakage Current Information for the Protection of the EnvironmentIntroduction and System Description Liebert GXT3-10000T220 control panelOverview of UPS devices and batteries Type Model # Nominal powerDevice Overview Unpacking Required Setup EquipmentInspection Unpacking the UPS and Site PreparationFloor Loading Access to AreaEnvironmental Conditions Inventory ListSuggested Cable Sizes InstallationElectrical preparations External Protection and Isolating DevicesTerminal Blocks for UPS Connecting Utility and LoadExternal Electrical Connections Rear Panel Cable Entry CoverInput and Output Connection Requirements Jumper removed for clarityCabinet Connecting Power CablesExternal Battery Cabinets Block Diagram OperationControls and Messages Lighted LEDs Fault Battery UPS On BypassControl Panel Flashing LEDMenu tree Displayed text-system block and main menu Control Battery Setup ParametersBattery setup parameters Test ReportFault Cause Corrective steps Fault IndicatorsFault indicators Maintenance Bypass Procedure Initial UPS Startup ProcedureUPS Shutdown Procedure Battery Test Return from Maintenance BypassMaintenance Breaker, Off Position Self-TestsMaintenance Test, Replacement and Disposal of BatteriesCleaning Replacement battery packDry Contact Any Mode ShutdownCommunication Interface Port CommunicationLow Battery Battery Mode ShutdownOn Battery Liebert IntelliSlot Communication CardsLiebert MultiLink Remote Emergency Power OffRepo switch connection diagram Problem Possible Cause Solution TroubleshootingTroubleshooting guide Specifications Liebert GXT3 specificationsDimensions, W x D x H, in. mm Battery cabinet specificationsTypical battery run times for the Liebert GXT3-10000T230 Internal Battery ParametersProduct Warranty Registration Twor k Ne tIs t Care