Page 15

Installation

3.7Connecting Power Cables

1.Open the UPS input breaker.

2.Open the UPS bypass breaker.

3.Set the maintenance breaker to the Bypass position.

4.Remove the electrical connection protective panel, if installed, from the rear UPS panel.

5.Connect loads to the output terminals as illustrated in Figure 7.

6.Connect the utility to the corresponding input terminals (see Figure 7).

If the bypass input is to be supplied separately, connect the bypass source to the corresponding bypass terminals.

If the UPS is supplied from a single feed, connect the factory-supplied jumper between terminal UPS Input-BYP and Bypass Input-L1.

3.8External Battery Cabinets

Up to four external battery cabinets may be connected to the Liebert® GXT3-10000T220. A cable to connect the battery cabinet and the Liebert GXT3-10000T220 is supplied with each battery cabinet.

Open the breaker before making battery cable connections.

Plug one end of this cable into the UPS and the other end into the battery cabinet—slotted fittings on each end ensure that the connection is properly made. If your UPS has an integrated battery, a compensating current may occur during connection. Once both ends of the cable have been connected, the circuit breaker on the external battery cabinet must be closed.

Figure 8 Liebert GXT3-10000T220 with External Battery Cabinet

External Battery Cabinet

Connector for

Battery Breaker

Liebert GXT3-240TVBATTCE

(Liebert GXT3-240TVBATTCE)

 

additional cabinet

 

External

Battery

Cabinet

Connector

UPS

External

Rear View

Battery

 

Cabinet

 

Rear View

! CAUTION

Battery maintenance must be performed only by authorized personnel who are properly trained and qualified.

External battery cabinets are hot-swappable; they can be replaced during normal UPS operation.

DO NOT connect or disconnect batteries when the UPS is in Battery Mode.

11

Image 15
Contents Liebert GXT3-10000T220 Page Table of Contents Communication MaintenanceImportant Safety Instructions Page Information for the Protection of the Environment Leakage CurrentLiebert GXT3-10000T220 control panel Introduction and System DescriptionType Model # Nominal power Device OverviewOverview of UPS devices and batteries Unpacking the UPS and Site Preparation Required Setup EquipmentInspection UnpackingInventory List Access to AreaEnvironmental Conditions Floor LoadingExternal Protection and Isolating Devices InstallationElectrical preparations Suggested Cable SizesRear Panel Cable Entry Cover Connecting Utility and LoadExternal Electrical Connections Terminal Blocks for UPSJumper removed for clarity Input and Output Connection RequirementsConnecting Power Cables External Battery CabinetsCabinet Operation Block DiagramFlashing LED Fault Battery UPS On BypassControl Panel Controls and Messages Lighted LEDsMenu tree Displayed text-system block and main menu Test Report Battery Setup ParametersBattery setup parameters ControlFault Indicators Fault indicatorsFault Cause Corrective steps Initial UPS Startup Procedure UPS Shutdown ProcedureMaintenance Bypass Procedure Self-Tests Return from Maintenance BypassMaintenance Breaker, Off Position Battery TestReplacement battery pack Test, Replacement and Disposal of BatteriesCleaning MaintenanceCommunication Any Mode ShutdownCommunication Interface Port Dry ContactLiebert IntelliSlot Communication Cards Battery Mode ShutdownOn Battery Low BatteryRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Troubleshooting Troubleshooting guideProblem Possible Cause Solution Liebert GXT3 specifications SpecificationsInternal Battery Parameters Battery cabinet specificationsTypical battery run times for the Liebert GXT3-10000T230 Dimensions, W x D x H, in. mmProduct Warranty Registration Care Ne tIs t Twor k