Liebert GXT3-10000T220 user manual Remote Emergency Power Off, Liebert MultiLink

Page 27

Communication

6.3.1Liebert® MultiLink®

Liebert MultiLink continually monitors the UPS and can shut down your computer or server in the event of an extended power failure.

Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot® SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown across the network with other computers running Liebert MultiLink when you purchase a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/Web Card and Liebert MultiLink License Kits, visit our Web site (www.liebert.com) or contact your local dealer or Emerson representative.

Several option cards are available for use in the Liebert IntelliSlot port of the Liebert GXT3. The Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the network.

The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four computers and coordinate shutdown in the event of a power failure.

The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers support for built-in shutdown for AS/400 systems.

! CAUTION

To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be shielded and run separate from all other power cables, where applicable.

6.4Remote Emergency Power Off

The UPS is equipped with a Remote Emergency Power Off (REPO) connector.

The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring codes and regulations.

REPO switch connection diagram

UPS ships with REPO jumper installed allowing the UPS to operate

1

2

Opening the REPO connection will disable the UPS. Manual restart using the front panel is required after the REPO connection is closed again.

1

2

 

 

Normally closed switch system (fail-safe)

! CAUTION

To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run separately from power cables.

23

Image 27
Contents Liebert GXT3-10000T220 Page Table of Contents Communication MaintenanceImportant Safety Instructions Page Information for the Protection of the Environment Leakage CurrentLiebert GXT3-10000T220 control panel Introduction and System DescriptionType Model # Nominal power Device OverviewOverview of UPS devices and batteries Unpacking the UPS and Site Preparation Required Setup EquipmentInspection UnpackingInventory List Access to AreaEnvironmental Conditions Floor LoadingExternal Protection and Isolating Devices InstallationElectrical preparations Suggested Cable SizesRear Panel Cable Entry Cover Connecting Utility and LoadExternal Electrical Connections Terminal Blocks for UPSJumper removed for clarity Input and Output Connection RequirementsConnecting Power Cables External Battery CabinetsCabinet Operation Block DiagramFlashing LED Fault Battery UPS On BypassControl Panel Controls and Messages Lighted LEDsMenu tree Displayed text-system block and main menu Test Report Battery Setup ParametersBattery setup parameters ControlFault Indicators Fault indicatorsFault Cause Corrective steps Initial UPS Startup Procedure UPS Shutdown ProcedureMaintenance Bypass Procedure Self-Tests Return from Maintenance BypassMaintenance Breaker, Off Position Battery TestReplacement battery pack Test, Replacement and Disposal of BatteriesCleaning MaintenanceCommunication Any Mode ShutdownCommunication Interface Port Dry ContactLiebert IntelliSlot Communication Cards Battery Mode ShutdownOn Battery Low BatteryRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Troubleshooting Troubleshooting guideProblem Possible Cause Solution Liebert GXT3 specifications SpecificationsInternal Battery Parameters Battery cabinet specificationsTypical battery run times for the Liebert GXT3-10000T230 Dimensions, W x D x H, in. mmProduct Warranty Registration Care Ne tIs t Twor k