Liebert GXT3-10000T220 user manual Communication Interface Port, Dry Contact, Any Mode Shutdown

Page 25

Communication

6.0COMMUNICATION

6.1Communication Interface Port

The Liebert® GXT3UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port and are assigned as follows.

6.2Dry Contact

The Dry Contact includes eight pins, as shown and defined in Figure 12.

Figure 12 Dry contact pin layout

1

2

3

4

(Low Battery

 

Warning)

 

(Any Mode

 

Shutdown)

 

 

 

 

 

 

(On- Battery

 

Warning)

 

(Battery Mode

 

Shutdown)

 

 

 

 

 

6.2.1Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static switch so that there is no power to the loads.

Any Mode Shutdown can be operated locally or remotely:

Local Any Mode Shutdown can be performed by shorting the pins in Set 3.

Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a remote location.

Activation of the Any Mode Shutdown will be logged as an event in the event history log.

NOTE

Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown. The current limited source (+12VDC, 50mA) will be available from UPS.

The connection to UPS for remote connection will be via terminal block connector.

Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.

! WARNING

When the Auto-enable output option is selected and the UPS output is disabled using the pins in Set 3, the Liebert GXT3-G’s output can turn On automatically and without warning if the connection of the pins in Set 3 is changed.

21

Image 25
Contents Liebert GXT3-10000T220 Page Table of Contents Communication MaintenanceImportant Safety Instructions Page Information for the Protection of the Environment Leakage CurrentLiebert GXT3-10000T220 control panel Introduction and System DescriptionDevice Overview Type Model # Nominal powerOverview of UPS devices and batteries Inspection Required Setup EquipmentUnpacking Unpacking the UPS and Site PreparationEnvironmental Conditions Access to AreaFloor Loading Inventory ListElectrical preparations InstallationSuggested Cable Sizes External Protection and Isolating DevicesExternal Electrical Connections Connecting Utility and LoadTerminal Blocks for UPS Rear Panel Cable Entry CoverJumper removed for clarity Input and Output Connection RequirementsExternal Battery Cabinets Connecting Power CablesCabinet Operation Block DiagramControl Panel Fault Battery UPS On BypassControls and Messages Lighted LEDs Flashing LEDMenu tree Displayed text-system block and main menu Battery setup parameters Battery Setup ParametersControl Test ReportFault indicators Fault IndicatorsFault Cause Corrective steps UPS Shutdown Procedure Initial UPS Startup ProcedureMaintenance Bypass Procedure Maintenance Breaker, Off Position Return from Maintenance BypassBattery Test Self-TestsCleaning Test, Replacement and Disposal of BatteriesMaintenance Replacement battery packCommunication Interface Port Any Mode ShutdownDry Contact CommunicationOn Battery Battery Mode ShutdownLow Battery Liebert IntelliSlot Communication CardsRepo switch connection diagram Remote Emergency Power OffLiebert MultiLink Troubleshooting guide TroubleshootingProblem Possible Cause Solution Liebert GXT3 specifications SpecificationsTypical battery run times for the Liebert GXT3-10000T230 Battery cabinet specificationsDimensions, W x D x H, in. mm Internal Battery ParametersProduct Warranty Registration Is t Ne tTwor k Care