Liebert GXT3-10000T220 Battery cabinet specifications, Model Number, Internal Battery Parameters

Page 30

Specifications

Table 10 Battery cabinet specifications

Model Number

GXT3-240TBATTCE

Dimensions, W x D x H, in. (mm)

 

Unit

31.5 x 11.81 x 26.57 (800 x 300 x 675)

Shipping

41.8 x 16.7 x 34 (1062 x 426 x 866)

 

 

Weight, lb (kg)

 

Unit

243 (110)

Shipping

309 (140)

 

 

Internal Battery Parameters

 

Type

Valve-regulated, non-spillable, lead acid

Quantity x V

2 x 20 x 12V

 

 

Battery Manufacturer, Part #

CSB HR1234R or Panasonic UP-RW1245

 

 

Temperature Limits, Batteries Only,

32 to 104 (0 to 40)

°F (°C)

 

Backup Time

See Table 11

Environmental

 

Operating Temp, °F (°C)

32 to 80 (0 to 27)

 

 

Storage Temp

5 to 104 (-15 to 40)

 

 

Transportation Temp, °F (°C)

5 to 122 (-15 to 50)

Relative Humidity

0-95% non-condensing

 

 

Operating Elevation

Up to 3281 ft (1000m) at 80°F (27°C) without derating

 

 

Agency

 

Safety

UL 1778, c-UL Listed

 

 

Transportation

ISTA Procedure 1B

 

 

Table 11 Typical battery run times for the Liebert® GXT3-10000T230

Number of Batteries,

 

 

 

 

Load %

 

 

 

 

Battery Cabinets

 

 

 

 

 

 

 

 

 

 

10%

20%

30%

40%

50%

60%

70%

80%

90%

100%

 

 

 

 

 

 

 

 

 

 

 

Internal Battery

81

39

22

15

11

8

6

5

4

3

 

 

 

 

 

 

 

 

 

 

 

Internal Battery + 1

190

127

81

60

46

39

32

26

22

18

External Battery Cabinet

 

 

 

 

 

 

 

 

 

 

Internal Battery + 2

316

162

136

106

82

69

52

48

44

39

External Battery Cabinets

 

 

 

 

 

 

 

 

 

 

Approximate discharge times are at 77°F (25°C) with a 100% resistive load.

26

Image 30
Contents Liebert GXT3-10000T220 Page Table of Contents Maintenance CommunicationImportant Safety Instructions Page Leakage Current Information for the Protection of the EnvironmentIntroduction and System Description Liebert GXT3-10000T220 control panelType Model # Nominal power Device OverviewOverview of UPS devices and batteries Unpacking Required Setup EquipmentInspection Unpacking the UPS and Site PreparationFloor Loading Access to AreaEnvironmental Conditions Inventory ListSuggested Cable Sizes InstallationElectrical preparations External Protection and Isolating DevicesTerminal Blocks for UPS Connecting Utility and LoadExternal Electrical Connections Rear Panel Cable Entry CoverInput and Output Connection Requirements Jumper removed for clarityConnecting Power Cables External Battery CabinetsCabinet Block Diagram OperationControls and Messages Lighted LEDs Fault Battery UPS On BypassControl Panel Flashing LEDMenu tree Displayed text-system block and main menu Control Battery Setup ParametersBattery setup parameters Test ReportFault Indicators Fault indicatorsFault Cause Corrective steps Initial UPS Startup Procedure UPS Shutdown ProcedureMaintenance Bypass Procedure Battery Test Return from Maintenance BypassMaintenance Breaker, Off Position Self-TestsMaintenance Test, Replacement and Disposal of BatteriesCleaning Replacement battery packDry Contact Any Mode ShutdownCommunication Interface Port CommunicationLow Battery Battery Mode ShutdownOn Battery Liebert IntelliSlot Communication CardsRemote Emergency Power Off Repo switch connection diagramLiebert MultiLink Troubleshooting Troubleshooting guideProblem Possible Cause Solution Specifications Liebert GXT3 specificationsDimensions, W x D x H, in. mm Battery cabinet specificationsTypical battery run times for the Liebert GXT3-10000T230 Internal Battery ParametersProduct Warranty Registration Twor k Ne tIs t Care