GenTran ATS2001R, ATS2002R, ATS2001D, ATS1001R Connecting the Low Voltage Cable to the Generator

Page 21

NOTE: Not all generators require four control wires to operate. Some may combine the CRANK and ON function in which case the CRANK wire is not required. Additionally, select generators are controlled by a 240VAC signal from the transfer switch. If you need assistance with your particular generator-transfer switch control connection, contact your distributor or Gen/Tran for control wiring instructions.

4.4 Connecting the Low Voltage Cable to the Generator

There is a terminal block in the wiring compartment of the generator to connect the power cables and the low voltage wire to control the generator. Some generators use 2, others 4 control wires. Refer to the generator installation manual for proper connection.

1.Connect the PIN 1 wire from the transfer switch to the battery “–“ (negative) terminal. If there is no battery terminal block, run the PIN 1 wire to the “–“ (negative) post on the battery itself.

2.Connect the PIN 2 wire from the transfer switch to the battery “+” (positive) terminal.

3.Connect the PIN 3 wire from the transfer switch to the ON/OFF terminal on the generator. This wire starts and runs the generator. If your generator has a 2 or 3-wire system, the PIN 3 wire should be installed with the PIN 2 wire as the other + (positive) wire on the battery.

4.Connect the PIN 4 wire from the transfer switch to the Crank or Start terminal (only used on generators having a separate Start terminal.) The PIN 4 wire is not used if there is no specific Crank/Start terminal on the generator.

4.5Installing and Wiring PowerPause™ Load Management Modules (optional)

Optional PowerPause™ Load Management Modules (Figure 4.5.1) are required when the load connected to the generator exceeds the generator capacity and dynamic load management is needed. Each PowerPause™ Load Management Module can control up to 2 loads; up to 3 Load Management Modules can be installed into each Control Module, 6 (240V) managed loads in total (or 12 x 120V loads). Load management priority

is determined at time of installation.

1.Remove Control Module from transfer switch. Refer to Figure 4.1.1.3.

a.Remove branch circuit breaker (if installed) opposite controller module.

b.Slide Control Module ½” towards circuit breaker bus stabs (towards center of enclosure).

c.Pull up outside end of Control Module ¾”so that controller module is tilted up about 30° degrees.

d.Pull Control Module off of circuit breaker bus stab.

2.Unplug all cables from the Control Module. Cable marking is not required, as connectors are uniquely keyed; each connector can only be inserted into its proper location.

3.Remove five (5) screws holding black plastic shield in place. Set aside screws. See Figure 4.5.3.

4.Rotate shield ¼ turn, align three (3) top holes and one (1) side hole to metal enclosure, re-install four (4) screws until tight, discard extra screw. See Figure 4.5.4.

5.Refer to completed TABLE 3.4 for POWERPAUSE™ LOAD MANAGEMENT CIRCUIT PRIORITY. Note the 1-6 position label on shield edge and three - 5 pin white plugs on Control Module circuit board. The priority of the managed load wired to the PowerPause™ Load Management Module is determined by the location the Module is installed on the control module circuit board, the lower the location #, the higher the priority (1=highest, 6=lowest). Install PowerPause™ Load Management Modules left-to- right, priority location 1-2 first, by inserting a PowerPause™ Load Management Module into left-side 5 pin plug and securing with provided #2x.25 Plastite screw. Repeat for up to 2 additional PowerPause™ Load Management Modules. Do not skip over priority locations: i.e. Use location 1-2 for the first Module, location 3-4 for a second Module and location 5-6 for a third Module. See Figure 4.5.5.

6.Observe mating connector on PowerPause™ Load Management Module(s) labeled NO-C-NC NO-C-NC. Based on the relay type selected to manage loads (Normally Open (NO) or Normally Closed (NC)), strip 18AWG, 300V relay control wire ¼” and insert and tighten into C (common) terminal and NO or NC terminal. Repeat for priority 2-6 loads. Tighten all wire connections to proper torque. NOTE: If wiring the Module in series to the 24VAC A/C compressor thermostat control circuit, wire to the C and NC terminals, if to a PowerPauseRelay Systems, wire to the C and NO terminals. See Figure 4.5.6.

21

Image 21
Contents Ovation Series Safety Precaution Definitions Table of Contents General Description IntroductionStandard Configurations Retrofit NEW Construction or Retrofit How the Ovation Series Automatic Transfer Switch WorksKey Components Model ATS1001D/RModel ATS2002R PowerPause Load Management Modules Optional User Interface Display UIDUtility and Generator Source Circuit Breakers Remote PowerPause Relay Box Optional Surge Protection Module OptionalStandards Compliance Compatible Generators Compatible EquipmentCompatible Circuit Breakers Compatible Circuit Breaker TypesOther Items YOU MAY Need Preparing for InstallationPowerpause Load Management Priority Page Installation and Wiring Internal Wiring Diagrams Models ATS2001D/R Internal Wiring Diagrams Model ATS2002R Then Pull UP Here As a Generator subpanel Models ATS1001D/R Center LoadFunction ON/OFF RUNConnecting the Low Voltage Cable to the Generator Page Programming the System Dial Name ModelNumber Service ResetTransfer GeneratorEnergizing the Transfer Switch Startup and TestingTesting the Transfer Switch Preliminary ChecksGenerator Battery Monitoring Re-Installing Covers and Labeling CircuitsProblem Possible Cause Solution Section TroubleshootingButton commands Battery fails toDelay between Exercise, orMaintenance Maintenance and ServiceExploded Views and Replacement Parts List Product RegistrationQTY PART# Description Type Model ATS1001DQTY PART# Description Type Model ATS1001RQTY Part Description Source Model ATS2001DQTY Description Source Model ATS2001RSource Model ATS2002RDescription 07/16/10 PN 530001 Rev D