GenTran ATS1001D manual User Interface Display UID, Utility and Generator Source Circuit Breakers

Page 9

1.5 Key Components: (continued)

Model ATS2001D/R**

Current

Transformers*

CT1 + CT2

Utility Main 200 Amp

 

 

 

 

 

 

 

 

 

Generator Main 125 Amp

[Branch

 

 

 

 

 

 

 

 

 

Circuit

 

Ground Bar

 

Breaker

 

 

 

 

 

 

 

 

 

Spaces]

Control Module (Stabs onto Bus)

To Set Generator Size

To Set Exercise Schedule

*Supplied with optional PowerPause™ Load Management Module (Model LSM)

**Not shown: ATSRK Relay Kit

Drive Motor Assembly

Actuator

Neutral Bar

User Interface Display

1.5.1 User Interface Display (UID)

The User Interface Display (UID), programming set switches and LEDs provide information about the transfer switch, generator and utility status. This UID is also used for programming the OVATION™ Series ATS for generator size, exercise intervals and other settings.

1.5.2 Utility and Generator Source Circuit Breakers

Siemens UL489 Listed 10K or 22K AIC utility circuit breakers act as Service Equipment disconnects and source feed wiring protection.

1.5.3 Mechanical Interlocked UTILITY and GENERATOR Main Circuit Breakers and Actuator

NEVER remove the mechanical interlocks/actuators unless the UTILITY or GENERATOR MAIN circuit breakers require replacement by a qualified service professional. UTILITY or GENERATOR MAIN circuit breakers are mechanically interlocked to prevent simultaneous UTILITY and GENERATOR power source feeds. Interlocks are automatically moved by a computer controlled actuator and motor, which may move the circuit breaker handles at any time.

1.5.4 PowerPause™ Load Management Modules (Optional)

Up to 6 connected loads based on parameters set up at installation are actively managed to optimize generator capacity utilization. As generator power capacity becomes available, the transfer switch will attempt to turn on each load controlled by PowerPause™ Load Management until the generator reaches 85% output utilization. Ideal for seasonal (i.e. air conditioning, pool equipment, etc) or intermittent (i.e. hot water heater, range, etc) loads. Contact your distributor or Gen/Tran for additional accessories information.

9

Image 9
Contents Ovation Series Safety Precaution Definitions Table of Contents General Description IntroductionStandard Configurations Retrofit NEW Construction or Retrofit How the Ovation Series Automatic Transfer Switch WorksKey Components Model ATS1001D/RModel ATS2002R PowerPause Load Management Modules Optional User Interface Display UIDUtility and Generator Source Circuit Breakers Remote PowerPause Relay Box Optional Surge Protection Module OptionalStandards Compliance Compatible Generators Compatible EquipmentCompatible Circuit Breakers Compatible Circuit Breaker TypesOther Items YOU MAY Need Preparing for InstallationPowerpause Load Management Priority Page Installation and Wiring Internal Wiring Diagrams Models ATS2001D/R Internal Wiring Diagrams Model ATS2002R Then Pull UP Here As a Generator subpanel Models ATS1001D/R Center LoadFunction ON/OFF RUNConnecting the Low Voltage Cable to the Generator Page Programming the System Dial Name ModelNumber Service ResetTransfer GeneratorEnergizing the Transfer Switch Startup and TestingTesting the Transfer Switch Preliminary ChecksGenerator Battery Monitoring Re-Installing Covers and Labeling CircuitsProblem Possible Cause Solution Section TroubleshootingButton commands Battery fails toDelay between Exercise, orMaintenance Maintenance and ServiceExploded Views and Replacement Parts List Product RegistrationQTY PART# Description Type Model ATS1001DQTY PART# Description Type Model ATS1001RQTY Part Description Source Model ATS2001DQTY Description Source Model ATS2001RSource Model ATS2002RDescription 07/16/10 PN 530001 Rev D