GE 70R-1000D manual How to Set the System Clock, CDT One Event Timer Exerciser

Page 14

How to Set the System Clock

How to Set the System Clock

Set System Clock, time and date

·If the clock is not set, the display will show SET SYSTEM CLOCK on the second line of the S1 OK screen.

·The S1 OK screen will show time (hours and minutes) on the second line if the system clock has been set. (Date on third line)

Setting the System Clock

(Start from S1 OK screen)

1.Remove battery protective white plastic strip near P relay. *

2.Press MORE then press SET.

3.Press MORE and scroll to SET SYSTEM CLOCK using the MORE key.

4.Press SEL.

5.ENTER ACCESS CODE located on the white label on the back of the controller.

6.Press SEL.

7.Use the up and down keys to change the hour value.

8.Press SAVE (this will enter this value and move cursor to minutes).

9.Use the up and down keys to change the minutes.

10.Press SAVE (this will enter this value and move cursor to month).

11.Use the up and down key up to change the month.

12.Press SAVE (This will enter this value and complete the clock setting).

13.Use the up and down keys to change the date.

14.Press SAVE (this will enter this value and move cursor to year).

15.Use the up and down keys to change year.

16.Press SAVE (this will enter this value and compete the clock setting).

17.To edit settings, press SEL and repeat steps 6-16.

18.If the setting is satisfactory, press MORE (unit then returns to the SET menu then press BACK, then ESC.)

*Replacement battery part #K-4100

Battery will last 5 years and provides power to retain clock function only (Controller functions without battery).

CDT One Event Timer Exerciser

Load / No-Load

One event Exerciser with adjustable Timer. Exercise duration can be set between 5 and 60 minutes in

1 minute increments. Can be configured to run every 1,7,14, or 28 days. Factory default is 20 minutes.

11.Press Up or Down to select XFR (Load Transfer) or NO XFR (No Load Transfer).

12.Press SAVE.

13.Press MORE repeatedly to BACK then S1 OK screen.

How to CONFIGURE (CFG) and Set (SET) the Timer Exerciser

1.Beginning from the S1 OK screen, press MORE then CFG.

2.Press MORE to scroll to CONFIG TIMER EXERCISER screen.

3.The third line of the CONFG TIMER EXERCISER will show either DAILY, WEEKLY, 14 DAY, 28 DAY, or OFF.

4.If the third line of the CONFG TIMER EXERCISER shows DAILY, WEEKLY, 14 DAY, or 28 DAY as desired, then proceed to step 10.

5.If the third line of the CONFG TIMER EXERCISER shows OFF or if another timer selection is desired, continue.

6.Press SEL.

7.Enter ACCESS code located on white label on the back of the controller.

8.Press UP or DOWN to select DAILY, WEEKLY, 14 DAY, or 28 DAY as desired.

9.Press SAVE.

10.Press MORE to scroll to CONFG TIMER EXERCISER (XFR) or (NO XFR).

Set (SET) the Exerciser:

14.Beginning from the S1 OK screen, press MORE then SET.

15.Press MORE repeatedly until EXER S2 RUN TIME screen.

16.Press SEL

17.Enter ACCESS code located on white label on the back of the controller.

18.Press SEL

19.Cursor is indicated as a line under character to

be changed. Change values with up and down keys.

20.Press SAVE when complete.

21.Press MORE repeatedly until SET USER SETUP then press BACK then ESC to the S1 OK screen.

14

ZTG/ZTGD Operation and Maintenance Manual (70R-1000D)

GE Zenith Controls

Image 14
Contents GE Zenith Controls Introduction Authorized ServiceTable of Contents Final Equipment Inspection Safety / InstallationEquipment Inspection and Storage MountingEngine Start Control Connections Installation cont’dPower Connections Installation cont’d GE Zenith Controls Initial EnergizationInitial Energization cont’d R E T E S TMX150 Microprocessor Controller MX150 ControllerMX150 Microprocessor Controller cont’d LCD & KeypadSource User Setting for Voltage & FrequencyStandard Features, Mstdg Option Pkg CalibrateS13 Std. Features, Mstdg Option Pkg. cont’dR50 Standard Features, Mexeg Option Pkg CDP replaces CDTOptional Accessories How to Set the System Clock CDT One Event Timer ExerciserCDT One Event Timer Exerciser cont’d How to Bypass Cancel an exercise during an exercise cycleCDP Clock Exerciser Load / No-Load Clock ExerciserMX150 User Setup CFG Menu Turn options on or OFF via keypad through the CFG menuMX150 User Setup SET Menu Change adjustable values through the SET menuMX150 User Setup System Info View System DataDelayed Transition TestingATS Testing Standard TransitionTimer Designations as they appear in the SET menu Sequence of OperationControls Power Supply CPS Standard and Delay TransitionDelayed Transition CPS Schematic Controls Power Supply CPS cont’dStandard Transition CPS Schematic Troubleshooting and Diagnostics General TroubleshootingTesting Maintenance and TestingInspection and Cleaning ServicingPower Panel and Replacement Parts Standard Transition 40 to 260 Amps Solenoid TypePower Panel and Replacement Parts cont’d Standard Transition 400 to 600 Amps Molded TypeStandard Transition 800 to 1200 Amps ARC Grid Removed for ClarityStandard Transition 1600 to 3000 Amps Stationary Contact Moveable ContactDelayed Transition 40 to 600 Amps AmpsDelayed Transition 800 to 1200 Amps SCR-EO Movable Contact Stationary ContactDelayed Transition 1600 to 3000 Amps Movable E3 Contact StationaryPage Page Page GE Zenith Controls