GE EPM 5200, EPM 5350 Relay, Protection and Pulse Output, EPM 5300P Relay Overview

Page 18

CHAPTER 3: ELECTRICAL INSTALLATION

3.7: Relay, Protection and Pulse Output

(This section applies only to the -NL or -NL2 Relay Option.)

EPM 5300P RELAY OVERVIEW

The EPM 5300P offers dry contact relay output capability. The EPM 5200P only offers KYZ pulse outputs and cannot be configured to trip contacts on events.

FAIL-SAFE MODE: The EPM 5300P -NL option gives the user an adjustable tripping bandwidth. The user specifies a range over which functions, such as frequency, phase relation and voltage, are acceptable. The relay releases during times of normal operation, and engages when functions are outside specified normal levels. The relay can be programmed to engage during normal operating conditions, and release outside specified normal range (particularly when power is lost). This is the fail-safe mode.

HYSTERISIS: The EPM 5300P -NL option also includes adjustable hysterisis. In addition to a time delay on activating any contact, the user may specify a lower level to release the relay, rather than releasing after the initial alarm point. This is ideal during load shedding when an alarm activates at a certain level and the user does not want to turn off the alarm until a much lower, safer level.

SETABLE DELAYS: After reaching the alarm point, a change in relay status may be delayed for 255 seconds. The user also has the option of allowing the device to change relay status without any delay. After the alarm condition passes, the relay can be stopped from returning to a normal condition for a programmable time. Each delay time is independent of one another.

AND/OR LOGIC: If several parameters are assigned to one relay, the user can trip the relay if all functions are out of limit (and programming), or if one function is out of limit (or programming). For example, if limits on Voltage, Kilowatts, and Phase Imbalance are programmed and tied to Relay 1, the user can either trip the relay if one function is out of limit, or if all functions are out of limit.

2 RELAYS & 1 KYZ PULSE OUTPUT -NL OPTION

The EPM 5300P's flexibility accesses a variety of relay options through the Programming Mode (see programming sections). The relay option package consists of three relays: two can be dedicated to alarm or controlled through communication (or both) and one for KYZ pulse output.

If the relays are controlled through communication, there are two different modes:

Lock ON

Relay will not be affected by any alarm condition.

Lock OFF

Relay will not be affected by any alarm condition.

If the relays are used for communication and alarm, there are four different modes:

Lock ON

Relay stays on regardless of any alarm condition.

Lock OFF

Relay stays off regardless of any alarm condition.

Free ON

Relay turns on unless other conditions force it off.

Free OFF

Relay turns off unless other conditions force it on.

Relay connection (see Figure 3.1, below): Form C relays, rated 250V, 5A–2 each.

KYZ relay output (Form C), rated 200V, 100mA–1 each.

14

EPM 5000 series Advanced Power Meters

GE Multilin

Image 18
Contents Digital Multifunction Power Monitors EPM 5200, 5300Page Table of Contents SET LIMITS/RELAYS ModeREFERENCE………………81 Chapter AC Power Measurement Single Phase SystemThree-Phase System Relationship between apparent, real Reactive powerConsumption, Demand and Poor Power Factor Poly Phase System 1 Delta, 2 WyeWaveform and Harmonics Sinusoidal Waveform a sin ω ⋅ tTotal Harmonic Distortion THD Chapter Mechanical Installation Diagram 2.1 Standard installationPort CT Connection Chapter Electrical InstallationConnecting the Current Circuit Helpful Debugging ToolsElectrical Connection Installation Connecting the Voltage CircuitConnection to the Main Power Supply Control Power Option Suffix CurrentList of Connection Diagrams 2L1 Line Back View IV. Three-Phase Four-Wire Wye with Direct Voltage and CTsThree Phase Four-Wire Wye with CT and PTs LoadVI. Single Phase with CT and PT Connection EPM 5300P-SVII. Dual-Phase with CTs and PTs VIII. Three-Phase Four-Wire WYE with 2.5 ElementRelay, Protection and Pulse Output EPM 5300P Relay OverviewRelays & 1 KYZ Pulse Output -NL Option KYZ Pulse Outputs NL2 Option Decimal Point Placement Change in Level KW/MWStandard Rate Table for Watts Voltage9999.0 Units W Hour 999.9 99.99 KYZ Relay Connection for -NL2 OptionRS-485 Chapter Communication InstallationRS-232C Connection for DB-9 FemaleRS-485 Hookup Diagram 2 wire Half Duplex RS-485 Hookup Diagram 2 wire Half Duplex Closed Loop RS-485 Hookup Diagram 2 wire Half Duplex Detail View RS-485 Hookup Diagram 4 wire Full Duplex RS-485 Hookup Diagram 4 wire Full Duplex Detail View Bottom View ShownNetwork of Instruments and Long Distance Communication ComputerModem Connected to Computer Originate Modem Programming the ModemDebugging Communication Problems Communication Installation Power A, B, C Chapter OverviewAccessing the Power Functions Accessing Voltage and Current PhasesAccessing %THD Functions Viewing Individual Phase Indication for Power Functions StepResetting Values Unprotected Reset Protected ResetResetting Hour Readings Accessing the LM1/LM2 Set LimitsThis display Press and hold down Voltage Phase Reversal and ImbalancePhase Reversal Phase Imbalance Indicates a VoltagePrint Operating Data Access ModesAppears, confirming a successful print command Press and hold Press Amps until a AppearsAccessing Firmware Version/LED Test Step Press and hold PHASE/NEXT Press Amps until 4 appearsPrint Programming Data Step Chapter Programming Overview General ProcedureSwitch Packs Groups Functions PacksProgramming Mode Data Entry Standard Numeric Data EntryChapter EPM 5200PFeature 5300P 5200P 5350P EPM 5300P vs. EPM 5200P vs. EPM 5350P5300P 5200P 5350P Password Entry Chapter Entering Programming ModeChecksum Error-Protective Self-Checking Algorithms Entering Programming ModeEntering Programming Mode Function Chapter Programming Group 0 Global Meter SetupGroup 0, Function 0-The Integration Interval FunctionGroup 0, Function 1-The Meter Address Group 0, Function 2-BAUD Rate Group 0, Function 3-System Configuration Group Function PackPack Switch Feature Segment Position Down +PFPrinting Option Open Delta System Installation ProgrammingModbus Plus Capability Disabling PreventsGroup 0, Function 3-Programming Procedure To change the System Configuration Switch SettingsSwitch C Description Relay ModeSwitch Description DefinitionsProgramming Steps Group 0-FUNCTION Number Description04.P Controls Relay 05.P Controls Relay 2 and 3 if NL4 To change the Relay Mode to either Fail-safe or Reset Group and Function Number Description To change Time Delays To program RelayGroup 0, Function 6-KYZ Parameter Selection Parameter DescriptionValue PER PER Watt Hour Selection KYZ Pulse KYZ Pulse Value06P FSW=9.999Situation 3 FSW=99.99 Situation 4 FSW=9.999Group 0, Function 7-Number of Phases Standard Factory SET-UP is THREE-PHASE FOUR-WIREFormulas Group and Function NumberTo change the Full Scale Settings Voltage Full ScalePress Volts to move decimal point Press Amps to store Group 1, Function 1-Amperage Full Scale CT T YPE Full ScaleStep Press Amps to begin Data Entry Sequence Example 3 14.4 KV/120, 1000/5 CT FSV=480 FSA=1000 a FSW one phase=480 V ⋅ 1000 aExample 2 480/120 PT, 1000/5 CT FSV=14.40 KV FSA=1000 aTo change the scale factor setting for wattage Programming Group High End Calibration-Volts AN, BN, CN Chapter Programming Group 2-METER CalibrationCalibration Requirements High End Calibration-Amps A, B, CVoltage Range Input Source Group 2 Value To change the calibration high end-Functions 0For Amps Low End Function Press MAX/MIN/LIMITS to end calibration procedure Example of LM1/LM2 SET Limits Time Delays & Relay ModeChapter Groups 4, 5 and 6-SET Limits and Relays Trip RelayGroup 4, Functions 0-3-LM1/LM2 Set Limits Group 4 Programming Format for Limit ConditionGroup 5, Functions 0-7-LM1/LM2 Set Limits There are 3 Switches to SET with Limits Digit Up Digit Down 0120LM1 LM2 Switch Value LED ABOVE/BELOW Relay Programming Group 6, LM1/LM2 Set LimitsDigit Up Digit Down 012.0 Limits or Relays Programming ProcedureLM1 LED LM2 LED Switch Level ABOVE/BELOW Relay Digit Down Digit Up 009.0Press Amps once to Disable the Limit Follow this step for Disabling LimitsSee to Exit Phase Reversal and Phase Imbalance ∃TRIP Relay 1 %TRIP Relay 2 &LEVEL ∋ENABLE/DISABLEVoltage Phase Imbalance Group 7, Function 0-Voltage Phase Reversal DetectionVoltage Phase Reversal Detection To change the phase reversal settingGroup 7, Function 1-Percentage Voltage Phase Imbalance To change the percentage voltage phase imbalanceSee to Exit Chapter Exiting Programming Mode Exiting Programming Mode Data Entry Sequence Entering the Programming ModeChapter Programming Quick Reference Programming GroupsGroup 0-Global Meter Setup Reserved SwitchesGroup 3 Calibration Ratios Group 1 Full Scale SetupGroup 2 Calibration Group 4 Volt/Current LimitsGroup 7 Imbalance/Reversal Limits Group 5 Power Function LimitsGroup 6 THD Limits Group 8 DC output CalibrationKEY Designations Programming Quick Reference Chapter Ethernet Option Ethernet ModuleEthernet Option Setup Description LED FunctionsNetwork Port Login Default IP AddressSetting the IP Address AutoIPNetwork Configuration ARP on WindowsTelnet to Port Configuration Parameters Baud RateGE Multilin