CHAPTER 9: PROGRAMMING GROUP 0 – GLOBAL METER SETUP
HOW TO USE KYZ PULSE VALUE TABLE FOR MULTIPLICATION:
SITUATION 1: FSW=9999. | SITUATION 2: FSW=999.9 |
• Selection is Multiply by 2 | • Selection is Multiply by 2 |
• This means that every .5 unit WH =1 pulse. | • This means that every .05 unit WH=1 pulse. |
• Unit=Kilo (see Group 1, Function 2) | • Unit=Kilo (see Group 1, Function 2) |
• Result: For every 1 KWH increment on the | • Result: For every 1 KWH increment on the |
counter, the meter will output 2 pulses. | counter, the meter will output 20 pulses. |
SITUATION 3: FSW=99.99
•Selection is Multiply by 20
•This means that every .0005 unit WH=1 pulse.
•Unit=Kilo (see Group 1, Function 2)
•Result: For every 1 KWH increment on the counter, the meter will output 2,000 pulses.
SITUATION 4: FSW=9.999
•Selection is Multiply by 20
•Unit=Kilo (see Group 1, Function 2)
•This means that every .00005 WH=1 pulse.
•Result: For every 1 KWH increment on the counter, the meter will output 20,000 pulses.
HOW TO USE THE KYZ PULSE VALUE TABLE FOR DIVISION:
SITUATION 1: FSW=9999. | SITUATION 2: FSW=999.9 |
• Selection is Divide by 10 | • Selection is Divide by 10 |
• This means that every 10 unit WH=1 pulse. | • This means that every 1 unit WH=1 pulse. |
• Unit=Kilo (see Group 1, Function 2) | • Unit=Kilo (see Group 1, Function 2) |
• Result: For every 10 KWH increment on the | • Result: For every 1 KWH increment on the |
counter, the meter will output 1 pulse. | counter, the meter will output 1 pulse. |
SITUATION 3: FSW=99.99
•Selection is Divide by 20
•This means that every .2 unit WH=1 pulse.
•Unit=Kilo (see Group 1, Function 2)
•Result: For every 1 KWH increment on the counter, the meter will output 5 pulses.
To change the KYZ pulse value:
SITUATION 4: FSW=9.999
•Selection is Divide by 20
•Unit=Kilo (see Group 1, Function 2)
•This means that every .02 WH=1 pulse.
•Result: For every 1 KWH increment on the counter, the meter will output 50 pulses.
MAX | AC VOLTS | ||
A B C A B | C | ||
MIN | |||
N N N B C A | |||
LM1 | |||
|
| ||
LM2 | AC AMPS |
| |
|
| ||
| A B C N |
| |
| POWER |
PF
KW
KVA
KVAH |
| KWH |
| FREQ |
| KVAR |
MAX/MIN | VOLTS | AMPS | POWER | PHASE |
LIMITS |
| NEXT |
MAX | AC VOLTS | ||
A B C A B | C | ||
MIN | N N N B C A | ||
LM1 | |||
|
| ||
LM2 | AC AMPS |
| |
|
| ||
| A B C N |
| |
| POWER |
|
|
| PF |
|
|
| KW |
|
|
| KVA |
KVAH | KWH | FREQ | KVAR |
MAX/MIN | VOLTS AMPS | POWER | PHASE |
LIMITS | NEXT |
| MAX |
|
|
|
|
|
|
|
|
|
|
| AC VOLTS | ||||||||
| MIN |
|
|
|
|
|
|
|
|
|
|
| A B C A B C | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| N N N B C A | |||||||||
| LM1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| LM2 |
|
|
|
|
|
|
|
|
|
|
| AC AMPS | ||||||||
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| A B C N | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| POWER | |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| PF | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| KW | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| KVA | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| KVAH |
|
| KWH |
|
|
| FREQ |
|
|
|
|
| KVAR | ||||||
|
|
|
|
|
|
|
MAX/MIN | VOLTS | AMPS | POWER | PHASE |
LIMITS |
| NEXT |
Step 1:
a. Enter Group Level of Programming Mode, (see Chp. 8).
b. Press MAX/MIN/LIMITS until 0. appears in upper display.
c. Press AMPS to activate the Group.
Step 2: | Step 3: |
a. Press MAX/MIN/LIMITS until 06.P | a. Press AMPS to change current |
appears in upper display. | setting. |
! The lower display indicates | ! The decimal point next to the 6 |
multiplication or division factor. | disappears. |
| b. Press MAX/MIN/LIMITS to |
| advance selections. |
| c. Press VOLTS to reverse. |
| (Until desired factor appears). |
!Division is indicated by div appearing in the middle display.
When middle display is blank, it indicates multiplication.
d. Press AMPS to store.
GE Multilin | EPM 5000 series Advanced Power Meters | 57 |