CHAPTER 3: ELECTRICAL INSTALLATION
OPTION 2: ISOLATING A CT CONNECTION REVERSAL USING VOLTAGE READINGS
!Remove potential connections to terminals 6 and 7. Observe the KW reading. It should be positive.
!If negative, reverse the CT wires on terminals 8 and 9.
Connect terminal number 6 potential. If KW decreases to about zero, reverse CT wires on terminals 10 and 11.
Connect terminal number 7 potential. If KW is
3.3: Connecting the Voltage Circuit
For proper meter operation, the voltage connection must be maintained. The voltage must correspond to the correct terminal.
The cable required to terminate the voltage sense circuit should have an insulation rating greater than 600V AC and a current rating greater than 0.1 A.
3.4: Selecting the Voltage Fuses
We strongly recommend using fuses on each of the sense voltages and the control power, although connection diagrams do not show them. Use a 1 Amp fuse on each voltage input.
The meter can handle a maximum voltage of 150V phase to neutral. PTs are required for higher voltages. Suffix
3.5: Connection to the Main Power Supply
The meter requires separate control power to operate. Listed are the five different power supply options and corresponding suffixes.
CONTROL POWER | OPTION SUFFIX | CURRENT |
120V AC | 115 A | 0.1 AAC |
240V AC | 230 A | 0.05 AAC |
12V DC | D4 | 0.10 ADC |
D | ||
125V AC/DC (universal) | D2 | 0.10 AAC or DC |
Table 3.2: Control Power and Current
Note: For
Note: Externally fuse power supply with a
3.6: Electrical Connection Installation
Choose the diagram that best suits your application and maintain the CT polarity. Follow the outlined procedure to verify correct connection. IMPORTANT: For PT connections only, short terminals 3 and 4. Connect local ground to terminal 3. This protects the unit from spikes and transients.
8 | EPM 5000 series Advanced Power Meters | GE Multilin |