Fortinet FortiGate-5000 manual FortiGate-5140 chassis back panel, Slot numbers

Page 17

FortiGate-5140-R chassis

FortiGate-5140 chassis back panel

Also visible on the front of the FortiGate-5140 chassis:

Electrostatic discharge (ESD) socket, used for connecting an ESD wrist or ankle band when working with the chassis.

Front cable tray, used for managing and securing ethernet and other cables.

Front accessible air filter.

Three hot swappable FortiGate-5140 cooling fan trays.

FortiGate-5140 chassis back panel

Figure 2 on page 17 shows the back panel of the FortiGate-5140 chassis. The back panel includes two hot-swappable redundant -48V/-60 VDC power entry modules (PEMs) labelled A and B. Fortinet ships the FortiGate-5140 chassis with PEM A and B installed. The PEMs provide redundant DC power connections for the FortiGate-5140 chassis and distribute DC power to the chassis slots and to the fan trays.

Figure 2: FortiGate-5140 chassis back panel

Back cable

tray

ESD

socket

Chassis

ground

connector

(green)

RTM

slot filler

panels

RTM

14

12

10

 

 

8

 

6

 

4

2

1

3

5

 

7

 

 

9

11

13

slot numbers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-48V/-60 VDC nom

 

RETURN

 

 

-48V/-60 VDC nom

 

RETURN

 

 

 

 

4

3

2

1

4

3

2

1

 

 

4

3

2

1

4

3

2

1

 

 

 

 

TERMINAL BLOCK COVER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remove terminal block cover and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

decable before removing PEM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

3

2

1

4

3

2

1

 

 

4

3

2

1

4

3

2

1

 

 

 

B PEM

 

 

 

 

 

 

 

 

 

A PEM

 

 

 

 

 

 

 

 

 

 

-48V/-60 VDC

 

RTN

 

 

-48V/-60 VDC

 

RTN

 

 

 

nom (black)

 

(red)

 

 

nom (black)

 

(red)

 

 

Power

Power

Entry Module B

Entry Module A

 

(terminal block

 

cover removed)

TERMINAL BLOCK COVER

Remove terminal block cover and decable before removing PEM.

If you require redundant power you should connect both PEMs to DC power. If redundant power is not required, you should connect PEM A to DC power. Each PEM has four -48V/-60 VDC connectors and 4 RTN connections. All eight of these connectors should be connected to DC power. Figure 2 on page 17 shows the terminal block cover removed from PEM A and the wiring required to connect PEM A to DC power. While operating the FortiGate-5140 both terminal block covers should be installed.

FortiGate-5000 Series Introduction

 

01-30000-83466-20090108

17

http://docs.fortinet.com/ Feedback

 

Image 17
Contents FortiGate-5000 Series Product updates, technical support, and FortiGuard servicesTrademarks Contents FortiGate-5020 chassis FortiGate-5050 chassisFortiGate-5001A security system FortiGate-RTM-XB2 systemFortiSwitch-5003 system FortiSwitch-5003A systemFortiGate-5001SX security system FortiGate-5005-DIST security systemContents FortiGate-5000 Series Introduction Revision History IntroductionRevision history FortiGate-5050-R chassis on FortiGate-5050 chassis on About the FortiGate-5000 series chassisAbout About the FortiGate-5000 series boardsFortiGate-5001FA2 security system FortiGate-RTM-XB2 moduleA FortiGate-5050 or FortiGate-5140 chassis Communication betweenFortiGate-5000 Series Introduction Fortinet documentation About Data Center DC powerCustomer service and technical support Register your Fortinet product FortiGate-5140-R chassis Slot FortiGate-5140 chassis front panelSlot numbers FortiGate-5140 chassis back panelPhysical description of the FortiGate-5140 chassis FortiGate-5140 chassis FortiGate-5140 chassis back panel RTN 21 x 19 x 16.8 in .3 x 48.3 x 42.7 cm FortiGate-5050-R chassis FortiGate-5050 front panel Power LEDFortiGate-5050 chassis back panel FortiGate-5050 back panelPhysical description of the FortiGate-5050 chassis FortiGate-5050 chassis physical description DimensionsFortiGate-5050 chassis FortiGate-5050 chassis Weight Physical description of the FortiGate-5050 chassis FortiGate-5020 front panel FortiGate-5020 chassisPower dissipation FortiGate-5020 physical description DimensionsFortiGate-5020 back panel Physical description of the FortiGate-5020 chassisFortiGate-5001A security system FortiGate-5001A-DW front panel Front panel LEDs and connectorsLists and describes the FortiGate-5001A LEDs LEDsLists and describes the FortiGate-5001A connectors ConnectorsBase backplane communication Fabric backplane communicationFortiGate-RTM-XB2 AMC modulesFortiGate-ASM-FB4 FortiGate-RTM-XB2 system FortiGate-RTM-XB2 power LED From the FortiGate-RTM-XB2 font panel includes a power LEDState Description Power Front panel LEDFortiGate-5005FA2 front panel FortiGate-5005FA2 security systemACT Lists and describes the FortiGate-5005FA2 board LEDsLink StatusAccelerated packet forwarding and policy enforcement Lists and describes the FortiGate-5005FA2 connectorsFA2 interfaces and active-active HA performance Base backplane gigabit communicationFortiGate-5005-DIST security system FortiGate-5001FA2-LENC front panel FortiGate-5001FA2-LENC security systemFortiGate-5001FA2-LENC board LEDs Lists and describes the FortiGate-5001FA2-LENC board LEDsPWR STAState Description Link Lists and describes the FortiGate-5001FA2-LENC connectorsBase backplane gigabit communication FortiGate-5001SX front panel FortiGate-5001SX security systemFortiGate-5001SX LEDs Lists and describes the FortiGate-5001SX board LEDsBase backplane gigabit interfaces Lists and describes the FortiGate-5001SX connectorsBase backplane gigabit interfaces FortiSwitch-5003A system FortiSwitch-5003A front panel MGMT, B1 Lists and describes the FortiSwitch-5003A front panel LEDsSH1 Base channel interfacesCLI Fabric channel interfacesBase 10G Base and fabric gigabit switching within a chassis FortiSwitch-5003A configurationsFront panel connectors FortiSwitch-5003A base channel 1 HA heartbeat communication Fabric 10-gigabit switching within a chassisBasic link aggregation configuration Layer-2 link aggregation and redundancy configurationsFortiSwitch-5003 system CLK ZREAbout the ZRE network activity LEDs ResetEXT FLT INT FLTETH0 Base backplane communicationsZRE0 ZRE1Base backplane communications Base backplane communications FortiGate-5005-DIST security system Basic FortiGate security system configurationExample basic FortiGate-5005-DIST security system FortiController-5208 I/O boardsFortiGate-5005FA2 worker boards FortiGate-5005-DIST security system chassis Where FortiGate-5005-DIST interface namesFortiGate-5005-DIST interface names FortiController-5208 system FortiController-5208 board LEDs Lists and describes the FortiController-5208 board LEDsPayload Operation DataManagement ControlD15, D16 Backplane gigabit interfacesC15, C16 COM1, COM2