Fortinet 5050-R manual FortiGate-5050 back panel, Rtm

Page 7

FortiGate-5050 chassis

FortiGate-5050 back panel

FortiGate-5050 back panel

Figure 2 shows the back of a FortiGate-5050 chassis. The FortiGate-5050 chassis back panel includes two redundant -48V to - 58V DC power input connectors labelled Input A and Input B. The power input connectors provide redundant DC power connections for the FortiGate-5050 chassis and distribute DC power to the fan tray and the FortiGate-5000 series boards installed in the FortiGate-5050 chassis. Each power input connector includes a 24 Amp circuit breaker that also functions as an on/off switch for the power input connector.

If you require redundant power you should connect both power input connectors to DC power. If redundant power is not required, you should connect power input connector A to DC power. When operating, the power input connectors are covered with clear protection plates.

Figure 2: FortiGate-5050 chassis back panel

5

4

3

2

1

RTM

slot filler

panels

Ground

Connector

(green)

Power

wire

fixture

INPUT A

-48V RTN (-DC IN)

24

AMP

Positive

-48V

(-DC in)

(RTN)

 

 

(black)

(red)

 

 

 

DC Power

 

Input A

 

 

INPUT B

 

 

 

-48V

 

 

 

RTN (-DC IN)

 

 

 

 

24

 

 

 

AMP

Positive

-48V

 

(-DC in)

(RTN)

 

 

(black)

(red)

 

 

 

ESD socket

DC Power

 

 

Input B

 

The back panel includes the FortiGate-5050 chassis ground connector which must be connected to Data Center ground. Use the power wire fixtures for securing and managing DC power wires. The FortiGate-5050 chassis also includes an ESD socket on the back panel.

For detailed information about connecting power to the FortiGate-5050 chassis, see “Connecting the FortiGate-5050 chassis to data center DC power and data center ground” on page 15 or “Connecting the FortiGate-5050 chassis to AC power using the FortiGate-5053 power converter tray” on page 17.

The back panel also contains 5 RTM slots numbered to correspond to the front panel slots. The RTM slots are available for FortiGate-5000 RTM modules such as the FortiGate-RTM-XB2 module. When the FortiGate-5050 chassis is shipped, these slots are covered by RTM slot filler panels.

FortiGate-5050-R Chassis Guide

 

01-30000-87717-20090108

7

http://docs.fortinet.com/ Feedback

 

Image 7
Contents FortiGate-5050-R FortiGate-5050-R Chassis Guide Contents Contents FortiGate-5050-R Chassis Guide FortiGate-5050 chassis FortiGate-5050 front panel Power LEDRTM FortiGate-5050 back panelFortiGate-5050 shelf managers Physical description of the FortiGate-5050 chassisShelf Manager fan and power control FortiGate-5050 shelf alarm panelUSER3 5050SAP Shelf alarm panel telco alarmsConnecting to the shelf manager CLI using a serial port Shelf manager command line interface CLIFortiGate-5050 Shelf Alarm Panel To use the shelf manager command line interface agent Clia About data center DC power Power connection and configurationRTN To connect the FortiGate-5050 chassis to data center ground Connecting the FortiGate-5050 chassis to data center groundLED FortiGate-5053 power converter tray front and back panelBasic power requirements Redundant FortiGate-5053 power converter trays Redundant FortiGate-5050 power suppliesRedundant FortiGate-5053 power converter trays FortiGate-5050-R Chassis Guide Red RTN to Black VDC to FortiGate-5053 Wiring the FortiGate-5053 power converter tray Turning on FortiGate-5050 chassis powerInserting 5000 series modules into a FortiGate-5050 chassis Mounting the FortiGate-5050 chassisAir flow FortiGate-5050 hardware procedures Fortinet documentation Customer service and technical supportRegister your Fortinet product Vcci