Fortinet 5050-R manual Basic power requirements

Page 19

Power connection and configuration

The back panel also includes three AC power connectors numbered 1, 2, 3. The AC connector numbering corresponds to the slot numbering showing in Figure 10. Each connector connects AC power directly to a FortiGate-5020/5050 power supply. The FortiGate-5053 can contain 1, 2, or 3 FortiGate-5020/5050 power supplies depending on your requirements. You should only connect AC power to the power supplies that are installed.

AC input power characteristics:

AC input voltage: 110 to 250 VAC

AC input current: 10A

Frequency: 47 to 63 Hz

Selecting the power supplies and power converter trays that you need for your FortiGate-5050 configuration

This section provides some basic information for determining how many FortiGate-5053 power converter trays and FortiGate-5020/5050 power supplies that you need, depending on the power requirements of your FortiGate-5050 chassis. This section provides guidelines only. Actual requirements may vary depending on your installation requirements. Contact Fortinet Technical Support if you need more information.

The FortiGate-5053 power converter tray contains space for up to three FortiGate-5020/5050 power supplies. A FortiGate-5020/5050 power supply converts AC power to -48 VDC power. Each FortiGate-5020/5050 power supply provides 800W of power.

The FortiGate-5053 power converter tray uses 2 + 1 power supply redundancy. If three FortiGate-5020/5050 power supplies are installed in a FortiGate-5053 power converter tray, the first two power supplies provide a total of 1600W (2 x 800W) of power. The third power supply is the redundant backup.

The maximum power output for a FortiGate-5053 power converter tray with FortiGate- 5020/5050 power supplies is 1600W; which can be achieved with two FortiGate- 5020/5050 power supplies. If you need 1600W of power and power supply redundancy, you can add a third FortiGate-5020/5050 power supply.

Individual power requirements vary. If 800W is enough power and redundancy is not required, you need one FortiGate-5053 power converter tray and one FortiGate- 5020/5050 power supply.

If 800W is sufficient but a redundant power supply is required, you can add a second FortiGate-5020/5050 power supply. This second power supply will also cover power requirements between 800 and 1600W. If you require redundant power greater than 800W you can add a third FortiGate-5020/5050 power supply.

Basic power requirements

To supply enough power for a FortiGate-5050 chassis with a total of five FortiGate modules and FortiSwitch modules you require one FortiGate-5053 power converter tray and two FortiGate-5020/5050 power supplies (see Figure 12). The FortiGate-5020/5050 power supplies are installed in FortiGate-5053 slots 1 and 2. This configuration supplies 1600W of power to the FortiGate-5020/5050 chassis.

Note: If your will not be filling all of the FortiGate-5050 slots you may not need both

FortiGate-5020/5050 power supplies.

FortiGate-5050-R Chassis Guide

 

01-30000-87717-20090108

19

http://docs.fortinet.com/ Feedback

 

Image 19
Contents FortiGate-5050-R FortiGate-5050-R Chassis Guide Contents Contents FortiGate-5050-R Chassis Guide FortiGate-5050 chassis FortiGate-5050 front panel Power LEDRTM FortiGate-5050 back panelFortiGate-5050 shelf managers Physical description of the FortiGate-5050 chassisShelf Manager fan and power control FortiGate-5050 shelf alarm panelUSER3 5050SAP Shelf alarm panel telco alarmsConnecting to the shelf manager CLI using a serial port Shelf manager command line interface CLIFortiGate-5050 Shelf Alarm Panel To use the shelf manager command line interface agent Clia About data center DC power Power connection and configurationRTN To connect the FortiGate-5050 chassis to data center ground Connecting the FortiGate-5050 chassis to data center groundLED FortiGate-5053 power converter tray front and back panelBasic power requirements Redundant FortiGate-5053 power converter trays Redundant FortiGate-5050 power suppliesRedundant FortiGate-5053 power converter trays FortiGate-5050-R Chassis Guide Red RTN to Black VDC to FortiGate-5053 Wiring the FortiGate-5053 power converter tray Turning on FortiGate-5050 chassis powerInserting 5000 series modules into a FortiGate-5050 chassis Mounting the FortiGate-5050 chassisAir flow FortiGate-5050 hardware procedures Fortinet documentation Customer service and technical supportRegister your Fortinet product Vcci