Connecting the FortiGate-5050 chassis to data center DC power and data center ground

Figure 8: Connecting a FortiGate-5050 power input connector to data center DC power

 

Data Center

Data Center

-48VDC

RTN connector

connector

RTN (positive)

red to Data

Center RTN

-48V (-DC in) black to Data Center -48VDC

INPUT A

-48V RTN (-DC IN)

Power wire fixture

Positive

(RTN)

(red)

24

AMP

-48 (-DC in) (black)

To connect a FortiGate-5050 power input connector to data center DC power

You need the following tools and equipment to connect a FortiGate-5050 power input connector to data center DC power:

A number 2 Phillips screwdriver.

An electrostatic discharge (ESD) preventive wrist or ankle strap with connection cord.

One black AWG-14 stranded wire with terminal lugs attached and labelled -48V.

One red AWG-14 stranded wire with terminal lugs attached and labelled RTN.

1Attach the ESD wrist strap to your wrist and to an ESD socket or to a bare metal surface on the chassis or frame.

2Loosen the screws and remove the protection plate.

3Insert the black -48V and red RTN wires through the power wire fixture (see Figure 8).

4Connect the black -48V power wire from the data center DC power source to the terminal on the FortiGate-5050 power input connector labelled (-DC in).

5Connect the red RTN return wire from data center RTN to the terminal on the FortiGate-5050 power input connector labelled RTN.

6Make sure the power wires are secured to the chassis using the power wire fixture and tie wraps if required.

7If required, label the black wire -48V.

8If required, label the red wire RTN.

9Re-attach the protection plate to the FortiGate-5050 power input connector.

FortiGate-5050-R Chassis Guide

1601-30000-87717-20090108http://docs.fortinet.com/ Feedback

Image 16
Contents FortiGate-5050-R FortiGate-5050-R Chassis Guide Contents Contents FortiGate-5050-R Chassis Guide FortiGate-5050 chassis Power LED FortiGate-5050 front panelFortiGate-5050 back panel RTMPhysical description of the FortiGate-5050 chassis FortiGate-5050 shelf managersFortiGate-5050 shelf alarm panel Shelf Manager fan and power controlUSER3 Shelf alarm panel telco alarms 5050SAPShelf manager command line interface CLI Connecting to the shelf manager CLI using a serial portFortiGate-5050 Shelf Alarm Panel To use the shelf manager command line interface agent Clia Power connection and configuration About data center DC powerRTN Connecting the FortiGate-5050 chassis to data center ground To connect the FortiGate-5050 chassis to data center groundFortiGate-5053 power converter tray front and back panel LEDBasic power requirements Redundant FortiGate-5050 power supplies Redundant FortiGate-5053 power converter traysRedundant FortiGate-5053 power converter trays FortiGate-5050-R Chassis Guide Red RTN to Black VDC to FortiGate-5053 Turning on FortiGate-5050 chassis power Wiring the FortiGate-5053 power converter trayInserting 5000 series modules into a FortiGate-5050 chassis Mounting the FortiGate-5050 chassisAir flow FortiGate-5050 hardware procedures Fortinet documentation Customer service and technical supportRegister your Fortinet product Vcci