Table 1. Configuration Mode Parameters
Parameter | LCD Message | Description | Default Settings |
Output Voltage Setting | O/P V Setting | To change the output voltage |
|
|
| • Select 208, 220, 230, or 240V for 240V models. | For 240V models: |
|
| You are prompted to save this setting. | O/P V= 230V |
|
|
|
|
Input Voltage Tolerance | I/P Bypass Set | Select the input voltage tolerance range before the UPS | I/P |
|
| goes to Battery mode: ±10%, |
|
|
| You are prompted to save this setting. |
|
Input Frequency | I/P F Setting | The | Freq |
|
| a narrower frequency range. Select ±7% for a wider |
|
|
| frequency range. |
|
|
| You are prompted to save this setting. |
|
HE Mode Setting | Select whether | HE Mode Off | |
|
| enabled, you must also select the input voltage range: |
|
|
| ±10% or ±15%. |
|
|
| While operating in |
|
|
| transfers to utility power when: 1) the input voltage is |
|
|
| outside ±10% or ±15% from nominal; 2) the input |
|
|
| frequency is greater than ±3%; or 3) the input line is |
|
|
| not available. |
|
|
| You are prompted to save this setting. If the setting is |
|
|
| not allowed, the LCD shows “I/P out limit” which means |
|
|
| the input voltage or frequency is not suitable. |
|
Free Run Mode | Free Run Mode | Select whether Free Run mode is On or Off. If enabled, | Free Run On |
|
| you must also select Bypass Disable or Bypass Enable. | (Bypass Disable) |
|
| This selection defines how your UPS runs when the input |
|
|
| frequency (from the utility) is outside the selected frequency |
|
|
| tolerance (set via the I/P F Setting, above), but is inside the |
|
|
| maximum frequency limits the UPS can accept before |
|
switching to Battery mode.
For example: If your 50 Hz UPS is set to the factory default window of ±5% before the UPS starts regulating the frequency.
•The output frequency tracks the input frequency exactly from 47.5 to 52.5 Hz.
•If input frequency is between 45 and 65 Hz, the output frequency is regulated by the UPS to exactly 50 Hz (±0.5 Hz). You are prompted to save this setting.
Alarm Silence | Alarm Silence | Select whether Silence is On or Off. If enabled, the UPS | Silence Off |
|
| silences the alarm for an existing fault. If the UPS status |
|
|
| changes, the alarm beeps, overriding the previous alarm |
|
|
| silencing. The alarm does not silence if there is a low |
|
|
| battery condition. |
|