14
5.7Relay Card
This interface provides true relay contact output to peripheral devices. Outputs are
Table 2. Relay Card (AS/400) Pin Assignment
| Pin Number | Signal Name | Definition |
| Direction | ||
| 1 | - | Isolated common to pins 2 & 3 | - | |||
| 2 | Line OK | Relay contact; closed to pin 1 | - | |||
| 3 | Line Failure | Relay contact; closed to pin 1 | - | |||
| 4 | - | Isolated common to pins 5 & 6 | - | |||
| 5 | Battery Normal | Relay contact; closed to pin 4 | - | |||
| 6 | Battery Low | Relay contact; closed to pin 4 | - | |||
| 7 | - | Isolated common to pins 8 & 9 | - | |||
| 8 | UPS Alarm | Relay contact; closed to pin 7 | - | |||
| 9 | UPS On/OK | Relay contact; closed to pin 7 | - | |||
| 10 | - | Isolated common to pins 11 & 12 | - | |||
| 11 | UPS Online/Inverter | Relay contact; closed to pin 10 | - | |||
| 12 | UPS on Bypass | Relay contact; closed to pin 10 | - | |||
| 13 | +12VDC | Signal supply +12VDC |
| Out | ||
| 14 | Signal GND | Signal ground - Common | - | |||
| 15 | UPS Shutdown | Minimum 5 seconds high level | In | |||
|
|
|
| signal (+12VDC) to perform |
| ||
|
|
|
| shutdown according to following |
| ||
|
|
|
| Relay Card Jumper settings: |
| ||
|
|
|
|
|
|
|
|
|
|
| JP1 (default) | JP2 |
|
| JP3 |
| UPS Normal |
| - | No response |
| Go to bypass mode, | |
|
|
|
|
|
| back online when | |
|
|
|
|
|
| shutdown pins opened | |
|
|
|
|
|
|
| |
| UPS on Battery |
| Output off after | Immediate output off |
| Immediate output off | |
|
|
| 120 sec. Back online | UPS shutdown in |
| UPS shutdown in | |
|
|
| on resumption of AC | 12 seconds |
| 12 seconds | |
|
|
| power |
|
|
|
|
|
|
|
|
|
|
|
|
6.0Installing Lansafe Software
Your UPS is supplied with a