Eaton Electrical 9120 Specifications, Electrical Input 240V Models, Electrical Output 240V Models

Page 20

17

8.0 Specifications

Eaton Powerware reserves the right to change specifications without prior notice.

This section provides the following specifications for the Powerware 9120 models:

Electrical input and output

Environmental and safety

Weights and dimensions

Battery

Table 4. Electrical Input

240V Models

Nominal Voltage

240V default;

208, 220, 230, 240V selectable

Voltage Range

160-276V for 208, 220, 230, 240V nominal

Nominal Frequency

50/60 Hz, ±5% user-selectable

Noise Filtering

MOVs and line filter for normal and common mode noise

Connections

91200700A:

10A, IEC-C14 input connector

 

91201000A:

10A, IEC-C14 input connector

 

91201500A:

10A, IEC-C14 input connector

 

91202000A:

10A, IEC-C14 input connector

 

91203000A:

16A, IEC-C20 input connector

Table 5. Electrical Output

 

 

 

240V Models

 

Power Levels

91200700A:

700 VA, 490W

(rated at nominal inputs)

91201000A:

1000 VA, 700W

 

91201500A:

1500 VA, 1050W

 

91202000A:

2000 VA, 1400W

 

91203000A:

3000 VA, 2100W

Regulation

Nominal output voltage ±2%

(Normal mode)

 

 

Regulation

Nominal output voltage ±3%

(Battery mode)

 

 

Voltage Waveform

Normal mode: Sine wave; <5% THD with full PFC and

 

nonlinear load

 

Output Connections

91200700A:

(4) Australian 10A

 

91201000A:

(4) Australian 10A

 

91201500A:

(4) Australian 10A

 

91202000A:

(5) Australian 10A

 

91203000A:

(5) Australian 15A

 

 

 

Image 20
Contents Powerware Powerware If You Have a Question Customer SupportTable of Contents Safety Instructions Important Safety InstructionsUPS Features Powerware 9120 Controls and IndicatorsVA and 1000VA Rear Panel VA Rear PanelConnector Quick Startup Do not use this connection for modems or telephonesDisplay Mode OperationUPS Front Panel LCD Message DescriptionStandby Mode Diagnostic TestsStarting the UPS on Battery Turning the UPS OnConfiguration Configuration ModeConfiguration Mode Parameters Parameter LCD Message Description Default SettingsConfiguration Mode Parameters Additional UPS Features Inverter ShutdownNetwork Transient Protector Load SegmentsCommunication Port Communication SlotSNMP/Web Adapter Communication Port Pin AssignmentInstalling Lansafe Software Pin Number Signal Name Definition DirectionRelay Card Relay Card AS/400 Pin AssignmentReplacing the Batteries How to Replace Internal Batteries Recycling the Used BatteryElectrical Output 240V Models SpecificationsElectrical Input 240V Models Environmental and Safety 240V Models Weights and Dimensions UPS 240V ModelsBattery 2000 VASilencing an Audible Alarm TroubleshootingAudible Alarms and UPS Conditions Troubleshooting LCD Message or Possible Cause Action Condition Over-Charge Warranty Warranty InformationPage Dandenong VIC Australia Standard Warranty Registration Eaton Powerware Australia/New Zealand Offices Web Site Customer Service Offices