19
Table 8. Battery
Configuration | 700 VA: | (2) 12V, 9 Ah internal batteries; 24 Vdc |
| ||||
| 1000 VA: | (3) 12V, 9 Ah internal batteries; 36 | Vdc |
| |||
| 1500 VA: | (4) 12V, 9 Ah internal batteries; 48 | Vdc |
| |||
| (8) 12V, 9 Ah internal batteries; 96 Vdc | ||||||
Type | Sealed, | ||||||
Charging | Approximately 4 hours to 90% usable capacity at nominal line | ||||||
| voltage after full load discharge |
|
|
| |||
Table 9. Battery Run Times (in Minutes) |
|
|
|
|
| ||
|
| Run Times at Full/Half Load by UPS VA Ratings | |||||
Number of Batteries | 700 VA | 1000 VA | 1500 VA | 2000 VA |
| 3000 VA | |
UPS Internal Batteries | 8/20 | 8/21 | 7/20 | 14/30 |
| 8/20 |
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.