22
Table 10. Troubleshooting (cont.)
LCD Message or | Possible Cause | Action |
Condition |
|
|
Low Battery | The battery is running low. | 2 minutes or less of battery power remains |
2 beeps every 5 seconds. |
| (depending on load and battery charge). |
|
| Prepare for a shutdown. Save your work and |
|
| turn off your equipment. The alarm cannot be |
|
| silenced. |
Replace Battery | The battery needs replacing. | See Section 7.0 "Replacing Batteries" to replace |
3 beeps every 5 seconds. |
| the battery. |
Low Charge | The battery voltage is low. | The UPS is charging the batteries and may not |
3 beeps every 5 minutes. |
| deliver full run time. The alarm continues until |
|
| at least two minutes of run time is available. |
Output Overload | Power requirements exceed |
2 beeps per second. | UPS capacity |
| minute or |
| seconds) or the load is defective. |
| The UPS switches to Bypass |
| mode. |
Remove some of the equipment from the UPS. The UPS automatically switches back to Normal mode when the capacity returns to an acceptable level. You may need to obtain a larger capacity UPS.
Battery Overload | The UPS is on battery, and | Shutdown is imminent (30 seconds). Save your |
2 beeps per second. | the power requirements | work and turn off your equipment. Turn off and |
| exceed UPS capacity (130% | unplug or remove utility power from the UPS. |
| for 10 seconds or >130% for | Remove some of the equipment from the UPS. |
| 1.5 seconds) or the load is | Restart the UPS. You may need to obtain a |
| defective. | larger capacity UPS. |
Site Fault | Ground wire connection | Have a qualified electrician correct the wiring. |
1 beep per second. | does not exist or the line | To disable this alarm, see Section 4.0 |
| and neutral wires are | "Configuration" |
| reversed in the wall outlet. |
|
Battery Test | The UPS is performing a | None. The UPS returns to Normal mode when |
| battery test. | it completes a successful battery test. |
UPS internal temperature | Shutdown is imminent. Save your work and turn | |
Constant beep. | is too high. | off your equipment. Turn off the UPS. Clear |
|
| vents and remove any heat sources. Ensure the |
|
| airflow around the UPS is not restricted. Wait at |
|
| least 5 minutes and restart the UPS. If the |
|
| condition persists, contact your service |
|
| representative. |