Table 1. Configuration Mode Parameters (cont.)
Parameter | LCD Message | Description | Default Settings |
Manual Battery Test | Manual Bat Test | To initiate a manual battery test, press the ↵ button | Battery Test |
|
| twice when “Manual Battery Test” is displayed on the |
|
|
| LCD. During the test the LCD displays ON BATTERY. |
|
|
| The UPS resets the automatic timer after a manual |
|
|
| battery test. The LCD displays “Battery not charged” |
|
|
| when UPS test is requested but the battery is not |
|
|
| fully charged. |
|
Manual UPS Test | Manual UPS Test | To initiate a manual UPS | UPS Test |
|
| twice. During the test, the LCD displays ON BATTERY. |
|
Site Wiring Fault Alarm | Site Fault Set | Select Enable or Disable. When enabled, the alarm sounds | Detect Enable |
|
| when the ground connection is missing or the line and |
|
|
| neutral wires are reversed in the wall outlet. |
|
Modem Support | Modem Support | This parameter is reserved for future use, and should not | No Modem Support |
|
| be modified by the user. |
|
Number of Extended | Bat Pack Num Set | Select the number of EBMs connected to the UPS: | Extern Pack: 0 |
Battery Modules |
| • For |
|
|
| • For |
|
|
| You are prompted to save this setting. Refer to the |
|
|
| documentation that came with your battery pack for |
|
|
| more information. |
|
Communications Lock- | COM Control | For greater levels of security, users may choose to have | Enable |
out | Cmds | the UPS disregard shutdown commands that come from |
|
|
| the power management software or other communication |
|
|
| sources. |
|
|
| • When disabled, the UPS does not accept a shut down |
|
|
| command via the communication port, USB port, or |
|
|
| communication slot adapter. |
|
|
| • When enabled, the UPS operates normally in response |
|
|
| to external commands. |
|
|
| You are prompted to save this setting. |
|
Load Segment Control | Load Group Set | Allows manual control of load segments (see “Load | Group 1On 2On |
|
| Segments” Section 5.3) |
|
|
| By repeatedly pressing the scroll button, the individual |
|
|
| load segments can be turned on and off. |
|
|
| CAUTION To prevent the unintentional shutdown of |
|
|
| specific load segments, confirm your selection before |
|
|
| pressing the ↵ button. |
|
Manual Bypass | Manual Bypass | This parameter is used to manually place the UPS in | Bypass OFF |
| GO | Bypass mode. |
|
Configuration Mode | Config Mode Set | This parameter is reserved for future use, and should not | EscapeConfigMode |
Setting |
| be modified by the user. The setting may be toggled |
|
|
| between EscapeConfigMode and Enter ConfigMode. 5.0 |
|
|
| It should always be set to EscapeConfigMode. |
|