Page 46

w w w . d e l l . c o m s u p p o r t . d e l l . c o m

Figure 10-3. DC PEM Label

Voltage 'good' LED Status LED

Handle

48V in

Status

Over Current Protector

Studs

Finger Barrier

CC-E600-PWR-DC

 

 

 

FN000

CAUTION - Use copper

95a

conductors only

 

-48/-60Vdc

75A

 

Locking Screws

NOTE: If there is a PEM failure (the PEM status LED is not lit or amber, major alarm LED is lit, and audible alarm sounds), the entire PEM must be replaced. There are no field serviceable parts inside the PEM unit.

WARNING: Do not remove the PEM safety cover until the power supplied by the remote power source is

OFF.

WARNING: To be completely sure that power has been turned off, use a voltmeter to measure the voltage across the negative (-) and positive (+) source DC leads. The measurement across the positive and negative leads should be zero (0) volts before you proceed with the replacement.

To remove a PEM:

Step Task

1Ensure that the remote power source is in the OFF position and that the PEM status LED and Voltage LED are off.

2Switch the Over Current Protector (located on the PEM front panel) to the OFF position.

3Loosen the retaining screw and remove PEM safety cover.

4Disconnect power cables attached to the PEM.

5Slide the PEM out of the slot.

6If you are replacing a PEM, go to Power Supply.

If you are not replacing the PEM, replace the empty slot with a PEM blank.

Removing and Replacing RPMs, Line Cards, or SFMs

WARNING: Do not remove a panel blank unless you are ready to install a line card, RPM, or SFM into that slot. If you remove a card, immediately replace the empty slot with a panel blank. Blanks are required to control airflow and electromagnetic interference.

WARNING: Electrostatic discharge (ESD) damage can occur when components are mishandled. Always wear an ESD-preventive wrist or foot-heel ground strap when handling RPMs, SFMs, or line cards. After you remove the original packaging, place RPMs, SFMs, and line cards on an antistatic surface.

46

Removing and Replacing Parts

Image 46
Contents E600i TeraScale Installation Guide Page Contents Powering Up System Boot W . d e l l . c o m s u p p o r t . d e l l . c o m Contents Information Symbols Information Symbols and Warnings1describes symbols contained in this guide About This GuideRelated Publications Release Notes for the E-SeriesSite Selection Site PreparationEquipment Rack and Cabinet Requirements DC Power Requirements Power Requirements2500W AC Power Requirements Storage RequirementsE600i System Operating OverviewE600i Chassis Front View with AC Power Supplies E600i Chassis Rear ViewE600i System Installation Process E600i Hardware Component Operating Requirements SummaryPage Installing the Equipment Rack Shelf Bar Installing the ChassisUnpacking the E600i System To install a equipment rack shelf bar Standard Front Chassis Rack MountingInstalling the Chassis into an Equipment Cabinet To install the chassis into a prepared rackPage Installing the Fan Tray Fan TrayFan Speed and Temperature Fan SpeedPower Supply Minimum Power Supply RequirementsAC Power Supply Units AC Power Supply UnitInstall the AC Power Supply Units Power Cord RequirementsTo install an AC power supply unit Remove the AC Power Supply To remove an AC power supply unitInstall the DC PEMs DC Power Entry ModulesCable and Connector Requirements To install a DC PEMRemoving the DC PEM Safety Cover Replace the DC PEMTo remove a PEM Page Line Cards and RPMs Installing RPMs, Line Cards, and SFMsUnpacking RPMsLine Cards Preparing and Installing the RPMs and Line CardsTo install line cards and RPMs Blank PanelsInstalling RPM into the E600i RPM Label and LEDs Installing a Second RPMRPM LEDs Installing Switch Fabric Modules SFMs Line Card LEDsInstalling SFMs 2defines the SFM front panel and LED displays SFM Front Panel and LEDsSFM Front Panel and LED Descriptions Page RPM Ports and Cables Connecting the Console and Auxiliary PortsRPM Ports Console Port RJ-45 Pin Assignments Cable and Adapter Pin AssignmentsAuxiliary Port RJ-45 Pin Assignments Accessing the Console with a DB-25 Adapter Accessing the Console with a DB-9 AdapterPin Assignments Between E600i Console and DB-25 Adapter RJ-45 to DB-25 Adapter Pin Modem Assignments Accessing the 10/100 Ethernet Management PortAccessing the Auxiliary Port by Modem 100 Ethernet Management Port LEDsTo supply power to the E600i system Powering UpSupplying Power PreparationBooting to the CLI Prompt Booting from the Bootuser PromptRemoving and Replacing Parts Removing and Replacing the Fan TrayRemoving and Replacing Power Modules Replacing 2500W AC Power SupplyRemoving the Power Cord Replacing DC PEMsRemoving and Replacing RPMs, Line Cards, or SFMs DC PEM LabelTo remove and install an SFM No linecard numberRemoving and Replacing the Air Filter Replacing the E600i Air FilterTo remove and replace the air filter Page Inserting the External Flash Memory Card Using a Flash Memory CardExternal Flash Memory Card Overview Removing the External Flash Memory CardCopying Files to the External Flash Formatting an External Flash CardDisplaying Files Stored on the External Flash Dir Command Example Page E600i System Boot Process System BootBooting from the Bootuser Prompt To configure the chassis from the Bootuser prompt HelpUse the boot change command to edit appropriate fields Show default-gateway default-gateway ip-address Force10 Page Alarms Table B-1. Alarm Events and ReportingAC Power Supplies and Alarms SFMs and AlarmsAlarms Alarms W . d e l l . c o m s u p p o r t . d e l l . c o m Chassis Physical Design System SpecificationsThis appendix contains the following major sections DC Power Entry Module Requirement AC Power Supply Unit RequirementsEnvironmental SFM and RPM Power Requirements Agency ComplianceJapan Vcci Compliance for Class a Equipment Electromagnetic Compatibility EMC Safety Standards and Compliance Agency CertificationsProduct Recycling and Disposal Figure C-1. The European Weee symbol ISupport Website Accessing iSupport ServicesTechnical Support This appendix contains these major sectionsContacting the Technical Assistance Center Request tabRequesting a Hardware Replacement To request replacement hardware, follow these stepsPage Page W. d e l l . c o m s u p p o r t . d e l l . c o m

E600I specifications

The Dell E600i stands as a robust and versatile solution in the realm of high-performance computing, designed to meet the demands of both enterprise environments and individual users. This workstation is characterized by its powerful processing capabilities, advanced graphics options, and extensive customization features that allow users to tailor the system to fit specific needs.

At the heart of the Dell E600i is its support for the latest multi-core processors, offering substantial performance for demanding applications, whether in data analysis, 3D modeling, or intensive computational tasks. Users can choose from a range of Intel Xeon or Core processors, ensuring that they can achieve optimal performance levels according to their workload requirements.

In terms of graphics, the E600i provides the option to integrate high-performance GPU selections from NVIDIA or AMD. This makes it particularly suitable for graphic design, video editing, and complex simulations. The inclusion of dedicated graphics cards not only enhances rendering capabilities but also supports advanced visualization technologies, which are essential for industries such as architecture, engineering, and media production.

One of the standout characteristics of the E600i is its expandability. With multiple expansion slots available, users can easily upgrade or integrate additional components to enhance performance or to adapt to new tasks. This system supports ample memory configurations, allowing for significant multitasking and overall system responsiveness.

In addition to its hardware capabilities, the Dell E600i leverages cutting-edge technologies to enhance usability and performance. Features such as Dell Precision Optimizer streamline workflow by automatically adjusting settings to optimize the performance of specific applications. Furthermore, Dell’s reliability in terms of build quality and support ensures that users can rely on their workstation for long durations without concern.

The E600i is also engineered with an eco-friendly focus, incorporating energy-efficient technologies that not only reduce operating costs but also minimize environmental impact. This attention to sustainability makes it an attractive option for businesses and professionals committed to responsible practices.

In conclusion, the Dell E600i is a high-performance workstation that brings together powerful processing, advanced graphics capabilities, and exceptional expandability. Its robust features and focus on usability make it a compelling choice for professionals in numerous fields, ensuring that they can tackle any project with confidence and ease.