3) Drain Timer
The Drain Timer is
SETTING |
| TIME | |
Dip Switch | Dip Switch |
|
|
No. 3 | No. 4 | T1 | T2 |
OFF | OFF | 10 seconds | 150 seconds |
ON | OFF | 10 seconds | 180 seconds |
OFF | ON | 10 seconds | 120 seconds |
ON | ON | 20 seconds | 180 seconds |
T1: Time to drain the Water Tank
T2: Time to restrain defrost completion
4) Drain Counter
CAUTION
Do not adjust the Drain Counter, or the Evaporator may freeze up.
The Pump Motor drains the Water Tank at the frequency determined by the Drain Counter. The Drain Counter is
SETTING |
| FREQUENCY | |
Dip Switch | Dip Switch |
| |
No. 5 |
| No. 6 |
|
OFF |
| OFF | every cycle |
ON |
| OFF | every 2 cycles |
OFF |
| ON | every 5 cycles |
ON |
| ON | every 10 cycles |
19