FieldServer FS-8700-78 RDBC, WRBC, Wrbx, Timing Parameters Column Title Function Legal Values

Page 10

Driver Manual

4.4Client Side Map Descriptors

4.4.1FieldServer Specific Map Descriptor Parameters

 

Column Title

Function

Legal Values

 

Map_Descriptor_Name

Name of this Map Descriptor

Up to 32 alphanumeric

 

 

 

characters

 

Data_Array_Name

Name of Data Array where data

One of the Data Array names

 

 

is to be stored in the

from “Data Array” section

 

 

FieldServer

above

 

Data_Array_Location

Starting location in Data Array

0 to maximum specified in

 

 

 

“Data Array” section above

 

Function

Function of Client Map

RDBC, WRBC, WRBX,

 

 

Descriptor

Passive

 

 

The use of the WRBX keyword

 

 

 

is recommended for DART

 

 

 

configurations as

 

 

 

communications are minimized.

 

4.4.2 Timing Parameters

 

 

 

 

 

 

 

Column Title

Function

Legal Values

 

Scan_Interval

Rate at which data is polled

>0.1s

4.4.3Driver Specific Map Descriptor Parameters

 

Column Title

Function

Legal Values

 

 

Node_Name

Name of Node to fetch data

One of the node names

 

 

 

from

specified in “Client Node

 

 

 

 

Descriptor” above

 

 

 

 

 

 

 

Length

Length of Map Descriptor

1 The length must always be

 

 

 

 

set to one.

 

 

Address

Starting address of read block

Not required for client

 

 

 

 

configuration. This parameters

 

 

 

 

is used in simulation

 

 

 

 

configuration only.

 

 

The following parameters apply only to the Dart Driver.

 

 

 

DA_Func*

Tell the driver to poll the device

Everything

 

 

 

for all the data that is available.

 

 

 

 

The data is device specific.

See table 4.4.3.1 for a map of

 

 

 

 

how the data is stored in the

 

 

 

Other uses of this parameter are

Fieldserver data arrays

 

 

 

permitted. These uses are

 

 

 

 

discussed in the Advanced

 

 

 

 

Topics section of this manual.

 

 

 

 

 

 

 

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 8

Image 10
Contents FS-8700-78 Dart Effective for all systems manufactured after January 18Table of Contents Performance Issues Driver Manual Dart Driver DescriptionProvided by user Hardware Connections Hardware Driver Manual Hardware Configuration Dart Present Column Title Function Legal Values Driver Manual Basic ConfigurationData Arrays Section Title ExampleDriver Manual Client Side Connections Section Title Using a Dart ? Do not specifyDefault 1 second NoneDriver Manual Client Side Nodes Section Title RDBC, WRBC, Wrbx Timing Parameters Column Title Function Legal ValuesDriver Manual Page Page 5.1 Array Locations of ‘Everything’ Driver Manual Driver Manual Driver Manual Driver Manual Unit Types Driver Manual Driver Manual Map Descriptor Example 2 Writing a Set-Point ReccomendationPage Driver Manual Chapter Page Column Title Function Legal Values DAFunc Parameter Permitted values Func Description Driver Parameter DAField Parameter Permitted valuesSee .4.5.1 for all Other keywords Driver Manual DAMethod Parameter Values and Notes MethodDriver Manual Advanced Example Driver Manual AdvancedExample DADI1Byte Extract 4 bytesStarting at Apply methodDAAI3 Unusedarray Driver Manual Dead Nodes Troubleshooting Tips Bad ValuesDriver Manual Related Documents Ignored MessagesDriver Manual Writing data to Dap Devices Driver Manual Revision Change Notices Rev1.06a-Rev0 Changes from previous releases