FieldServer FS-8700-78 instruction manual Array Locations of ‘Everything’

Page 14

Driver Manual

4.4.5Map of How Data Aire Device Data is stored in a Data Array

In the example of 4.4.1 the Fieldserver listens passively for all possible data from the device called ‘unit1’ and stores the data in an array called ‘DA_01’.

The data that is obtained from ‘unit1’ is dependent on the type of device. Irrespective of the device type the arrangement of data, stored in DA_01, is fixed. If a data field cannot be obtained from ‘unit1’ then the array is left with a zero value for that data field.

Table 4.4.5.1: Array Locations of ‘Everything’

In the following table the array location indicates the offset in the data array at which a data field can be found. (This offset is relative to the offset specified in the map descriptor.) The columns headed 2,3 … indicate the unit types for which the data fields are available. For example: The field ‘d_temp’ can be read from unit types 2,5,6,7,9 but not from any of the other unit types. It is beyond the scope of this manual to describe each field and to indicate valid ranges. Such information should be obtained from the Data Aire Corporation.

‘x’ Indicates Read only

‘X’ Indicates a point that can be read & written. ‘w’ Indicates a write only point.

Array

 

Num

 

 

 

 

 

 

 

 

Location

Method Elements

Data Field

2

3 4 5 6 7

8

9 14 15 Message Type

1

1

1

Zone

 

w w w w w w w w

w Dap-Config

2

1

1

Inhibit

 

w w w w w w w w

w Dap-Config

3

4

1

unitType

x

x x x

x

x

x

x x

x Dap-Unit

4

2

1

temp

x

x

x

x

 

x

Dap-Stat

5

2

1

hum

x

x

x

x

 

x

Dap-Stat

6

2

1

d_temp

x

x

x

x

 

x

Dap-Stat

7

3

8

mode

x

x

x

x

 

x

Dap-Stat

23

3

8

hold

x

x

x

x

 

x

Dap-Stat

39

1

1

cs_on

x

x

x

x

 

x

Dap-Stat

40

1

1

hs_on

x

x

x

x

 

x

Dap-Stat

41

1

1

valvePCT

x

x

x

x

 

x

Dap-Stat

42

1

1

hVlvPCT

x

x

x

x

 

x

Dap-Stat

43

4

14

errors

x

x

x

x

 

x

Dap-Stat

57

2

1

hiTemp

x

x

x

x

 

x

Dap-Stat

58

2

1

loTemp

x

x

x

x

 

x

Dap-Stat

59

2

1

hiHum

x

x

x

x

 

x

Dap-Stat

60

2

1

loHum

x

x

x

x

 

x

Dap-Stat

61

1

1

chilled_water

x

x

x

x

 

x

Dap-Stat

62

1

1

compressor_config

x

x

x

x

 

x

Dap-Stat

FieldServer Technologies 1991 Tarob Court, Milpitas, California 95035 (408) 262-2299 fax: (408) 262-9042

Visit our website: www.fieldserver.com E-mail: support@fieldserver.com

Page 12

Image 14
Contents FS-8700-78 Dart Effective for all systems manufactured after January 18Table of Contents Performance Issues Driver Manual Dart Driver DescriptionProvided by user Hardware Connections Hardware Driver Manual Hardware Configuration Dart Present Column Title Function Legal Values Driver Manual Basic ConfigurationData Arrays Section Title ExampleDriver Manual Client Side Connections Section Title Using a Dart ? Do not specifyDefault 1 second NoneDriver Manual Client Side Nodes Section Title RDBC, WRBC, Wrbx Timing Parameters Column Title Function Legal ValuesDriver Manual Page Page 5.1 Array Locations of ‘Everything’ Driver Manual Driver Manual Driver Manual Driver Manual Unit Types Driver Manual Driver Manual Map Descriptor Example 2 Writing a Set-Point ReccomendationPage Driver Manual Chapter Page Column Title Function Legal Values DAFunc Parameter Permitted values Func Description Driver Parameter DAField Parameter Permitted valuesSee .4.5.1 for all Other keywords Driver Manual DAMethod Parameter Values and Notes MethodDriver Manual Advanced Example Driver Manual AdvancedExample DADI1Byte Extract 4 bytesStarting at Apply methodDAAI3 Unusedarray Driver Manual Dead Nodes Troubleshooting Tips Bad ValuesDriver Manual Related Documents Ignored MessagesDriver Manual Writing data to Dap Devices Driver Manual Revision Change Notices Rev1.06a-Rev0 Changes from previous releases