FieldServer FS-8700-78 Func Description Driver Parameter, DAField Parameter Permitted values

Page 27

Driver Manual

IN addition to the ‘Everything’ keyword indicated in chapter 4 the following specific query functions are implemented.

Func.

Description

Driver Parameter

Protocol Id.

‘1’

DART Config Query

DA_Func = dart-config

 

49

‘2’

Dart Psswd Query

DA_Func = dart-password

50

'3'

DAP Config Command DA_Func = dap-config

 

51

'4'

DAP Log Query

DA_Func = dap-log

 

52

'5'

DAP Unit-Type Query

DA_Func = dap-unit

 

53

'6'

DAP Stat Query

DA_Func = dap-stat

 

54

'7'

DAP Xtra Query

DA_Func = dap-xtra

 

55

'8'

DAP Menu Query

DA_Func = dap-menu

 

56

'A'

Chiller Stat Query

DA_Func = chiller-stat

 

65

'B'

Chiller Xtra Query

DA_Func = chiller-xtra

 

66

'C'

Chiller Menu Query

DA_Func = chiller-menu

67

‘D”

Dart Status

DA_Func = dart-status

 

68

'E'

DAP80 Menu Query

DA_Func = dap80-menu

69

'G'

DAP Analog Query

DA_Func = dap80-analog

71

'H'

DAP Channels Query

DA_Func = dap80_channles

72

Each of the above queries returns a complex set of data consisting of many sub-fields. Contact Data-Aire for a complete listing of the data composite returned.

The following special / diagnostic functions are also implemented.

Driver Parameter

Protocol Id.

DA_Func = All-Listen

11

DA_Func = Ack

6

DA_Func = Dart-Transparant

2

DA_Func = Dart-Opaque

3

DA_Func = Test-Echo

16

DA_Func = Test-No-Echo

15

DA_Func = Unit-Talk

13

With the exception of the Unit-Talk command, these are nodeless commands.

When using any of these special commands no other DA_* fields need be specified.

The operation of these functions is as follows ;

All-Listen instructs the all units in the network to switch their relays to the listen position. Those units already in the listen position will do nothing. Those in the talk position will first echo the all-listen command and then switch their relays to the listen position. A pause of 0.15 seconds is required after the transmission of this command, to allow the units time to switch their mechanical relays.

6.1.2DA_Field Parameter - Permitted values.

Legal values depend on the value of DA_Func.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 (408) 262-6611 fax: (408) 262-9042

Visit our website: www.sierramonitor.com E-mail: sierra@sierramonitor.com Page 25

Image 27
Contents Effective for all systems manufactured after January 18 FS-8700-78 DartTable of Contents Driver Manual Dart Driver Description Performance IssuesProvided by user Hardware Connections Hardware Driver Manual Hardware Configuration Dart Present Example Driver Manual Basic ConfigurationData Arrays Section Title Column Title Function Legal ValuesNone Using a Dart ? Do not specifyDefault 1 second Driver Manual Client Side Connections Section TitleDriver Manual Client Side Nodes Section Title Timing Parameters Column Title Function Legal Values RDBC, WRBC, WrbxDriver Manual Page Page 5.1 Array Locations of ‘Everything’ Driver Manual Driver Manual Driver Manual Driver Manual Unit Types Driver Manual Reccomendation Driver Manual Map Descriptor Example 2 Writing a Set-PointPage Driver Manual Chapter Page Column Title Function Legal Values DAFunc Parameter Permitted values DAField Parameter Permitted values Func Description Driver ParameterSee .4.5.1 for all Other keywords Method Driver Manual DAMethod Parameter Values and NotesDriver Manual Advanced Example DADI1 Driver Manual AdvancedExampleApply method Extract 4 bytesStarting at ByteDAAI3 Unusedarray Driver Manual Ignored Messages Troubleshooting Tips Bad ValuesDriver Manual Related Documents Dead NodesDriver Manual Writing data to Dap Devices Rev1.06a-Rev0 Changes from previous releases Driver Manual Revision Change Notices