FieldServer FS-8700-39 instruction manual Appendix D. EST3 ECP Connection Statistics

Page 20

FS-8700-39 EST3 Driver Manual

Page 20 of 21

 

 

Appendix D. EST3 ECP Connection Statistics:

The EST3 ECP protocol has two distinct levels:

A poll-response connection is maintained by the EST panel acting as the master. The bytes transferred in this process are displayed on the FieldServer as SCADA bytes transmitted and received.

The FieldServer acts as a client by inserting requests into its response messages; the EST panel then inserts the requested data into its subsequent polling messages. The bytes transferred in this process are displayed on the FieldServer as PLC bytes transmitted and received.

The following statistics are available on the Driver Aspects screen when viewing Connection Details (select the EST Connection in Connection Overview, and press space repeatedly to page to this screen):

Statistic Name

Description

DLL Rx Char

Data Link Layer Bytes Received

DLL Rx Msg

Data Link Layer Messages Received

DLL Tx Char

Data Link Layer Bytes Transmitted

DLL Tx Msg

Data Link Layer Messages Transmitted

DLL Timeouts

Data Link Layer Timeouts

DLL IC Timeouts

Data Link Layer Inter-Character Timeouts

DLL Streaming

Data Link Layer Streaming Errors

DLL Bad Replies

Data Link Layer Bad Replies

DLL Link Control

Data Link Layer Link Control Events

Gateway Type

ECP Gateway Type I/II/III

Data Rx Char

Data Bytes Received

Data Rx Msg

Data Messages Received

Data Tx Char

Data Bytes Transmitted

Data Tx Msg

Data Messages Transmitted

Conn Rx Char

Total Bytes Received on Connection

Conn Rx Msg

Total Messages Received on Connection

Conn Tx Char

Total Bytes Transmitted on Connection

Conn Tx Msg

Total Messages Transmitted on Connection

Delta Rx Char

Delta Message Bytes Received

Delta Rx Msg

Delta Messages Received

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 20
Contents Driver Manual FS-8700-39 EST3 ECP Applicability & EffectivityTable of Contents Required 3rd Party Configuration EST3 DescriptionProvided By the Supplier of 3rd Party Equipment Hardware ECP Type III with TextHardware Connections FieldServerP1UINT16 Configuring the FieldServer as a EST3 ClientData Arrays Client Side Connection Descriptors Client Side Node DescriptorsEST3 EST1 EST3Driver Related Map Descriptor Parameters RDBC, Wrbc 3, WrbxPage Map Descriptor Example Appendix A.2. Setting up Multiple Parameters Appendix A.4. Report and Delta ServiceAppendix A. Driver Notes Appendix A.1. PanelMasks Appendix A.3. PriorityAppendix A.4.1. Example Configuration using Delta Mode only DaalarmDATEST1 DatroubleAppendix A.5.3. ESTTypesUpdate Appendix A.5. Optional Data ArraysAppendix A.5.1. Relay Confirmation State Appendix A.5.2. ESTTypesDAAppendix A.5.5. ESTReportType Appendix A.6. Object Types and Required Parameters PartitionAppendix A.7. Set Date and Time To Panel FS-8700-39 EST3 Driver Manual Appendix C. EST3 Data Format Appendix C.1. Input data format Page Appendix C.2. Output data format Appendix D. EST3 ECP Connection Statistics Appendix E. Driver Error Messages