Appendix A. Driver Notes

Appendix A.1. PanelMasks:

The 8 PanelMask parameters combine to form a 64-bit field in which each bit denotes an EST panel in the network. Commands that use the PanelMasks are executed by each panel for which the corresponding bit is set. The Map Descriptor need only define non-zero bytes in the PanelMask. Typically this will be EST_Panel_Mask_1 with a value of 1.

Appendix A.2. Setting up Multiple Parameters

The multiple parameters required by a command must be stored in consecutive locations in the Data Array specified by the Map Descriptor, starting at the specified Data_Array_Offset. All parameters must be set up before the EST command is executed. This is done using a Block Write (if supported by the protocol originating the data) – all parameters are set up in a single write operation, and the EST command is triggered with all values in place.

Appendix A.3. Priority:

The write priority has the possible values of Set, Latch, Low, Medium, and High. These are encoded as 00h, 01h, 02h, 03h and 04h respectively.

Appendix A.4. Report and Delta Service:

The EST ECP3 Report and Delta services report point status slightly differently. The FieldServer EST3 driver deals with these differences as follows:

Report Service (regular polling):

The full 16-bit point status is stored to the Read Map Descriptor’s Data Array. If optional Data Arrays are configured, then the point status is also interpreted according to its Alarm, Trouble, Supervisory or Monitor status and the corresponding Data Array is updated. See Appendix A.5 for detail.

Delta Service (unsolicited messages):

Delta Service messages do not provide the same 16-bit status value as supplied by the Report Service. For this reason, ONLY the optional Data Arrays will be updated when a Delta message is received. Delta messages will therefore only have an effect when optional Data Arrays have been configured. See 0 for detail.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com

Image 10
Contents Driver Manual FS-8700-39 EST3 ECP Applicability & EffectivityTable of Contents Provided By the Supplier of 3rd Party Equipment Hardware Required 3rd Party ConfigurationEST3 Description ECP Type III with TextHardware Connections FieldServerP1Data Arrays Configuring the FieldServer as a EST3 ClientUINT16 EST3 Client Side Connection DescriptorsClient Side Node Descriptors EST1 EST3 Driver Related Map Descriptor Parameters RDBC, Wrbc 3, WrbxPage Map Descriptor Example Appendix A. Driver Notes Appendix A.1. PanelMasks Appendix A.2. Setting up Multiple ParametersAppendix A.4. Report and Delta Service Appendix A.3. PriorityDATEST1 Appendix A.4.1. Example Configuration using Delta Mode onlyDaalarm DatroubleAppendix A.5.1. Relay Confirmation State Appendix A.5.3. ESTTypesUpdateAppendix A.5. Optional Data Arrays Appendix A.5.2. ESTTypesDAAppendix A.5.5. ESTReportType Appendix A.6. Object Types and Required Parameters PartitionAppendix A.7. Set Date and Time To Panel FS-8700-39 EST3 Driver Manual Appendix C. EST3 Data Format Appendix C.1. Input data format Page Appendix C.2. Output data format Appendix D. EST3 ECP Connection Statistics Appendix E. Driver Error Messages